Verified by manufacturer 9 months ago
Constructionline Gold
Certificate type
ISO 9001 Quality Management
Certificate type
smas WORKSAFE
Certificate type
Warringtonfire
Certificate type
Fire shutter for masonry or structural steel up to 240 minutes fire integrity performance. Fully CE marked to BS EN 16034 and BS EN 13241. Third party Installation Certification with IFC.
Suitable for installation within the following structures:
The fire shutters are manufactured and produced in accordance with the parameters and technical aspects indicated within the specifications, which were submitted to the Warrington Fire Research Establishment. The shutters are constructed to Fire Testing in accordance with BS EN 1634-1 and full compliance with the new Fire Standard BS EN 16034:2014. This product can be fitted to a rigid structure and is CE marked.
Features and benefits:
Endplates:
The endplates are fixed to a steel fixing angle which spans the full height of the shutter, which in turn is fixed back to the wall construction. Accordingly, the angles are slotted for expansion with an anchor point located at the bottom of the angle.
Guides:
Constructed from minimum 50 mm straight channel galvanized guide mounted on 75 x 50 mm mild steel angle (minimum). For shutters of increased width compared with the tested to provide for expansion the depth of each guide rail shall be increased by 5 mm for every 1 m increase in width.
Hood:
Formed from 20 swg steel sheet, with the top leg slotted for expansion. Dependent on the fire rating of the shutter (one hour only) and the size of the opening (hood support brackets are no longer able to be used to reduce the barrel diameter). The EXAP provide for the use of a canopy (specific appropriate restrictions apply).
Release mechanism:
Fusible Link/Manual reset solenoid/Auto reset Solenoid Alternatively, Audio Visuals are available, again to be linked to the fire alarm, this unit offers the facility of a time delay, which flashes and sounds to warn that the fire shutter is closing.
Color | Other Guidance for specification option: Unlimited standard and non-standard RAL colours. |
Finish | Galvanized Powder-coated |
Material | Steel |
Shape | Rectangle |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Warranty description | One year Guidance for specification option: 12 month standard guarantee against parts and labour. |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
Standard | Internal fire-rated roller shutter CE marked to BS EN 13241 and BS EN 16034.Guidance for specification option: Available with third party installation certification for UK projects. |
Opening sizes | Manufacturer guidanceMaximum size (w x h): 8000 x 6900 mm. Permitted opening sizes for a CE marked fire shutters rely on approval from BS EN 15269-10. Height, width, substrate and required performance are assessed in a series of matrices. Please always confirm that the desired fire resistance can be achieved (by width, by height, by substrate) as per A1 Shutter's extended application to BS EN 15269-10 with the manufacturer. |
Format | Fire shutter. |
Arrangement | Single vertical rectangular configuration. |
Performance | |
Fire performance | |
Fire resistance | Up to 240 minutes.Guidance for specification option: Up to 240 minutes depending on width, height and structure (substrate). |
Smoke leakage | Manufacturer guidanceSmoke leakage to BS EN 1634-3 is not available on a fire shutter. Refer to A1S Group fire and smoke curtain range for this requirement. |
Watertightness | No performance declared. |
Acoustic performance | No performance declared. |
Frame and guides | |
Material | Galvanized steel. |
Finish | Polyester powder-coating.Guidance for specification option: Angles, barrel and end plates are painted. Galvanized.Guidance for specification option: Guides. |
Colour | BS 4800.RAL.Manufacturer guidanceSubject to availability. Consult manufacturer for details and insert requirements. |
Shutter curtain | |
Lath material | 76 mm curved steel scroll laths interlocked with steel end locks and galvanized 'T' section bottom rail. |
Profile | Curved. |
Finish and colour | Galvanized.BS 4800.Guidance for specification option: Polyester powder coating. RAL.Guidance for specification option: Polyester powder coating. Any RAL colour available, insert requirements. |
Execution | Manufacturer guidanceThird Party certified installation scheme from International Fire Consultants. Consult manufacturer for details. |
Operation | Electrically operated 1PH/ 3PH - Hand chain override. |
Accessories | Audio/ visual device. Guidance for specification option: Audio Visuals are available, again to be linked to the fire alarm, this unit offers the facility of a time delay, this flashes and sounds to warn that the fire shutter is closing. Fusible Link. Manual Reset Solenoid. Auto Reset solenoid. |
Contains Red List materials | No |
Country of material origin | Europe Guidance for specification option:
|