NBS Source
I'm a manufacturer

A1S Flameshield Fire Shutter 240 JM - Fire Shutter (With External Motor)

Verified by manufacturer 9 months ago

A1 Shutters Ltd Third party certifications:
  • Constructionline Gold

    Constructionline Gold

    Certificate type

  • ISO 9001 Quality Management

    Certificate type

  • smas WORKSAFE

    smas WORKSAFE

    Certificate type

  • Warringtonfire

    Warringtonfire

    Certificate type

Fire shutter for masonry or structural steel up to 240 minutes fire integrity performance. Fully CE marked to BS EN 16034 and BS EN 13241. Third party Installation Certification with IFC.

Jump to:
+44 (0)1204 383839 Website

Application

Suitable for installation within the following structures:


  • Masonry (maximum 240 minutes integrity fire performance).
  • Steel (maximum 240 minutes integrity fire performance).

Description

The fire shutters are manufactured and produced in accordance with the parameters and technical aspects indicated within the specifications, which were submitted to the Warrington Fire Research Establishment. The shutters are constructed to Fire Testing in accordance with BS EN 1634-1 and full compliance with the new Fire Standard BS EN 16034:2014. This product can be fitted to a rigid structure and is CE marked.


Features and benefits:

  • Warrington Element Fire Research Centre No. 421378. Masonry/Brickwork/Concrete Up to 240 minutes.
  • Extended Application under BS EN 15269-10: 2011 WF 421375.
  • Certificate of Constancy of Performance - 1121-CPR-RA5009.
  • CE marked to BS EN 16034.
  • CE marked to the machinery directive.
  • Decorative RAL finishes available.
  • External type motor.


Endplates:

The endplates are fixed to a steel fixing angle which spans the full height of the shutter, which in turn is fixed back to the wall construction. Accordingly, the angles are slotted for expansion with an anchor point located at the bottom of the angle.


Guides:

Constructed from minimum 50 mm straight channel galvanized guide mounted on 75 x 50 mm mild steel angle (minimum). For shutters of increased width compared with the tested to provide for expansion the depth of each guide rail shall be increased by 5 mm for every 1 m increase in width.


Hood:

Formed from 20 swg steel sheet, with the top leg slotted for expansion. Dependent on the fire rating of the shutter (one hour only) and the size of the opening (hood support brackets are no longer able to be used to reduce the barrel diameter). The EXAP provide for the use of a canopy (specific appropriate restrictions apply).


Release mechanism:

Fusible Link/Manual reset solenoid/Auto reset Solenoid Alternatively, Audio Visuals are available, again to be linked to the fire alarm, this unit offers the facility of a time delay, which flashes and sounds to warn that the fire shutter is closing.

General information

Color

Other

Guidance for specification option:

Unlimited standard and non-standard RAL colours.

Finish

Galvanized

Powder-coated

Material

Steel

Shape

Rectangle

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

One year

Guidance for specification option:

12 month standard guarantee against parts and labour.

Uniclass

Pr_30_59_84_30 Fire-resisting roller shuttersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Fire-resisting roller shutters

Standard

Internal fire-rated roller shutter CE marked to BS EN 13241 and BS EN 16034.

Guidance for specification option:

Available with third party installation certification for UK projects.

Opening sizes

-

Manufacturer guidance

Maximum size (w x h): 8000 x 6900 mm.


Permitted opening sizes for a CE marked fire shutters rely on approval from BS EN 15269-10. Height, width, substrate and required performance are assessed in a series of matrices. Please always confirm that the desired fire resistance can be achieved (by width, by height, by substrate) as per A1 Shutter's extended application to BS EN 15269-10 with the manufacturer.

Format

Fire shutter.

Arrangement

Single vertical rectangular configuration.

Performance

-

Fire performance

-

Fire resistance

Up to 240 minutes.

Guidance for specification option:

Up to 240 minutes depending on width, height and structure (substrate).

Smoke leakage

-

Manufacturer guidance

Smoke leakage to BS EN 1634-3 is not available on a fire shutter. Refer to A1S Group fire and smoke curtain range for this requirement.

Watertightness

No performance declared.

Acoustic performance

No performance declared.

Frame and guides

-

Material

Galvanized steel.

Finish

Polyester powder-coating.

Guidance for specification option:

Angles, barrel and end plates are painted.

Galvanized.

Guidance for specification option:

Guides.

Colour

BS 4800.

RAL.

Manufacturer guidance

Subject to availability. Consult manufacturer for details and insert requirements.

Shutter curtain

-

Lath material

76 mm curved steel scroll laths interlocked with steel end locks and galvanized 'T' section bottom rail.

Profile

Curved.

Finish and colour

Galvanized.

BS 4800.

Guidance for specification option:

Polyester powder coating.

RAL.

Guidance for specification option:

Polyester powder coating. Any RAL colour available, insert requirements.

Execution

-

Manufacturer guidance

Third Party certified installation scheme from International Fire Consultants. Consult manufacturer for details.

Operation

Electrically operated 1PH/ 3PH - Hand chain override.

Accessories

Audio/ visual device.

Guidance for specification option:

Audio Visuals are available, again to be linked to the fire alarm, this unit offers the facility of a time delay, this flashes and sounds to warn that the fire shutter is closing.

Fusible Link.

Manual Reset Solenoid.

Auto Reset solenoid.

Sustainability data

Contains Red List materials

No

Country of material origin

Europe

Guidance for specification option:

  • Germany.
  • Latvia.
  • United Kingdom.

Third party certifications

Constructionline Gold

Constructionline Gold

Constructionline Gold

ISO 9001 Quality Management

ISO 9001 Quality Management

ISO 9001 2015 (Issue 5)

smas WORKSAFE

smas WORKSAFE

SMAS 2023 (SSIP)

Warringtonfire

Warringtonfire

Certificate of Constancy of Performance (AVCP) CE marked fire shutters 60-240 minutes

Literature

A1S Flameshield Fire Shutter 240 JM Specification

A1S Flameshield Fire Shutter 240 JM Specification

Flameshield 240 JM Fire Shutter

Flameshield 240 JM Fire Shutter

Flameshield Fire Shutter 240 JM Reveal Fix

Flameshield Fire Shutter 240 JM Reveal Fix

Case studies

Required Testing and Certification Regime For CE marked fire shutters

Required Testing and Certification Regime For CE marked fire shutters