93PM-G2-100(200) - UPS 100 kW (PF 1.0)
Certificate of Conformity
Certificate type
Uninterruptible power supply (UPS) unit with high efficiency, modular and scalable to support critical infrastructure.
Suitable for use in:
The Eaton 93PM G2 UPS provides protection, security and flexibility in an efficient, modular and scalable uninterruptible power supply system. It is a second generation three-phase 93PM UPS solution for colocation data centers to increase capacity and power protection in line with demand.
Features and benefits:
Color | Black  | 
Finish | Matt  | 
Material | Steel  | 
Shape | Rectangle  | 
Length | 990 mm  | 
Width | 800 mm  | 
Height | 1987 mm  | 
Warranty description | One year  | 
Uniclass | |
CAWS | W53/380 Power supply units W53/380 Power supply units  | 
SKU Code | 93PM-G2-100(200)  | 
Classification data | |
Standards | To BS EN IEC 62040-1 and BS EN IEC 62040-3.  | 
Mode of operation | On-line.  | 
Configuration | Parallel with bypass. Guidance for specification option: Up to four units.  | 
Efficiency | |
Overall (minimum) | <97% at 100% load.  | 
Eco mode (minimum) | >99%.  | 
Load compatibility | Suitable for use with loads operating at any power factor (leading or lagging) up to 0.99.  | 
Input | |
Nominal voltage | 220/ 380 V, 230/ 400 V and 240/ 415 V. Manufacturer guidanceUser configurable.  | 
Frequency | 50/ 60 Hz. Manufacturer guidanceUser configurable.  | 
Power factor | >0.99.  | 
Total harmonic distortion (THD) | <2.5%.  | 
Inverter output | |
Nominal voltage | 220/ 380 V, 230/ 400 V and 240/ 415 V. Guidance for specification option: User configurable.  | 
Total harmonic distortion (THD) | <1% at 100% linear load. Guidance for specification option: 
  | 
Nominal frequency | 50/ 60 Hz.  | 
Overload capability | 110% for 60 minutes. 125% for 10 minutes. 150% for 1 minute.  | 
Maintenance bypass | Internal fully interlocked.  | 
Batteries | |
Location | Within UPS equipment enclosure. Separate battery enclosures.  | 
Type | Lead-acid valve-regulated (VRLA) to BS EN 60896-22 and BS EN 61056-1. Guidance for specification option: As standard. Nickel-cadmium. Wet cell batteries. Supercapacitors.  | 
Voltage | 384–528 V. Guidance for specification option: (32–44 blocks).  | 
Controls, indicators and alarms | |
LCD display | Information from UPS.  | 
Communications and signalling | USB.  | 
Enclosure | |
Ingress protection (minimum) | To BS EN 60529, IP20.  | 
Material and construction | |
Type | Steel.  | 
Finish | Matt.  | 
Colour | Black.  | 
Weight | 404 kg.  | 
Power output | 100 kW.  | 
Contains Red List materials | No  | 
Country of material origin | Finland  | 
Country of product manufacture | Finland  | 
Material | Steel  | 
Expected Life | 15 year  |