Verified by manufacturer 1 day ago
93PM-G2-50(200) - UPS 50 kW (PF 1.0)
Certificate of Conformity
Certificate type
Uninterruptible power supply (UPS) unit with high efficiency, modular and scalable to support critical infrastructure.
Suitable for use in:
The Eaton 93PM G2 UPS provides protection, security and flexibility in an efficient, modular and scalable uninterruptible power supply system. It is a second generation three-phase 93PM UPS solution for colocation data centers to increase capacity and power protection in line with demand.
Features and benefits:
Color | Black |
Finish | Matt |
Material | Steel |
Shape | Rectangle |
Length | 990 mm |
Width | 800 mm |
Height | 1987 mm |
Warranty description | One year |
Uniclass | |
CAWS | W53/380 Power supply units W53/380 Power supply units |
SKU Code | 93PM-G2-50(200) |
Classification data | |
Standards | To BS EN IEC 62040-1 and BS EN IEC 62040-3. |
Mode of operation | On-line. |
Configuration | Parallel with bypass. Guidance for specification option: Up to four units. |
Efficiency | |
Overall (minimum) | <97% at 100% load. |
Eco mode (minimum) | >99%. |
Load compatibility | Suitable for use with loads operating at any power factor (leading or lagging) up to 0.99. |
Input | |
Nominal voltage | 220/ 380 V, 230/ 400 V and 240/ 415 V. Manufacturer guidanceUser configurable. |
Frequency | 50/ 60 Hz. Manufacturer guidanceUser configurable. |
Power factor | >0.99. |
Total harmonic distortion (THD) | <2.5%. |
Inverter output | |
Nominal voltage | 220/ 380 V, 230/ 400 V and 240/ 415 V. Guidance for specification option: User configurable. |
Total harmonic distortion (THD) | <1% at 100% linear load. Guidance for specification option:
|
Nominal frequency | 50/ 60 Hz. |
Overload capability | 110% for 60 minutes. 125% for 10 minutes. 150% for 1 minute. |
Maintenance bypass | Internal fully interlocked. |
Batteries | |
Location | Within UPS equipment enclosure. Separate battery enclosures. |
Type | Lead-acid valve-regulated (VRLA) to BS EN 60896-22 and BS EN 61056-1. Guidance for specification option: As standard. Nickel-cadmium. Wet cell batteries. Supercapacitors. |
Voltage | 384–528 V. Guidance for specification option: (32–44 blocks). |
Controls, indicators and alarms | |
LCD display | Information from UPS. |
Communications and signalling | USB. |
Enclosure | |
Ingress protection (minimum) | To BS EN 60529, IP20. |
Material and construction | |
Type | Steel. |
Finish | Matt. |
Colour | Black. |
Weight | 361 kg. |
Power output | 50 kW. |
Contains Red List materials | No |
Country of material origin | Finland |
Country of product manufacture | Finland |
Material | Steel |
Expected Life | 15 year |