NBS Source
I'm a manufacturer

801PHEx Optical Smoke + Heat Detector

Verified by manufacturer 2 months ago

ADT Fire and Security

Intrinsically safe addressable optical smoke and heat detector.

Jump to:
Website

Application

  • The detectors may only be used in conjunction with an
  • IF800Ex Interface Module and a Pepperl+Fuchs KFD0-CSEx1.54 galvanic isolator.
  • The detectors are for use in potentially explosive gas and dust atmospheres (zone 0 gas, zone 20 dust).

Description

The 801PHEx Intrinsically Safe Optical Smoke and Heat

Detector forms part of the 800Ex Intrinsically Safe Series of

MX Addressable Fire Detectors. The detector plugs into an

MUBEx 4” Universal Base or 5B 5” Universal Base.

The detector is designed to transmit, to a remote Minerva MX/T2000 fire controller, digital signals which represent status of the optical smoke and heat elements of the detector.


Software within the controller is used to interpret the returned optical and heat values to raise alarm or other appropriate response according to the type of detector configured in ‘MX CONSYS’.


The detectors are designed to comply with EN/IEC 60079-

0:2006, EN/IEC 60079-11:2007 and EN/IEC61241-

11:2006 for Intrinsically Safe apparatus.


Features and benefits:

  • The optical smoke detector can be selected in one of two logic modes as follows: Normal and fastlogic modes.
  • The detector may be used as two separate detectors using two loop addresses.
  • Day/ night switching.
  • Sensitivity switching.
  • Self-test facility.


The mode of detector may be:

  • Mode 1 - Optical smoke only detector (sensitivity High, Normal or Low)
  • Mode 2 - HPO smoke detector (sensitivity High, Normal or Low)
  • Mode 3 - Optical (sensitivity High, Normal or Low) plus heat fixed temperature 60°C (A2S)
  • Mode 4 - Heat only normal ambient R-o-R (A1R) detector (no sensitivity selection)
  • Mode 5 - Heat fixed temperature 60°C (A2S) (no sensitivity selection)
  • Mode 6 - HPO (sensitivity High, Normal orLow) and heat fixed temperature 60°C (A2S).

General information

Color

White

Other

Guidance for specification option:

Pantone colours.

Shape

Circle

Width

109 mm

Guidance for specification option:

Diameter

Height

43 mm

Uniclass

Pr_75_80_30_64 Point heat detectorsPrimary

CAWS

W90/327 Point heat detectors

Specification data - Point heat detectors

Standard

To EN 54-5 and -7, EN50130-4, EN 61000-6-3, EN/IEC 60079-
0:, EN/IEC 60079-11 and EN/IEC61241-11.

Third-party certification

Certified ATEX code: Ex II 1 GD Cenelec code: Ex ia IIC T5/Ex iaD 20 T100°C. IECEx BAS 07.0063X.

Power source

From loop.

Manufacturer guidance

  • Loop Voltage: 18–24 V.
  • Quiescent current: 350 μA typical.
  • Alarm current: 3 mA typical.

Operating temperature

-25 to +70°C.

RelativeHumidity

95% (non-condensing).

Base

MUBEx 4” Universal Base.

5B 5” Universal Base.

Colour:

White.

BIM objects

Platform Compatible Version
Revit
-

1

Literature

516.800.530 801PHEx Optical Smoke + Heat Detector

516.800.530 801PHEx Optical Smoke + Heat Detector

Similar products from ADT Fire and Security

835H Heat Detector

835H Heat Detector

835P Photo Detector

835P Photo Detector

835PC 3oTec Triple Sensor Detector

835PC 3oTec Triple Sensor Detector

835PH Photo Heat Detector

835PH Photo Heat Detector

855H Heat Detector With Built-in Line Isolator

855H Heat Detector With Built-in Line Isolator

855P Photo Detector With Built-in Line Isolator

855P Photo Detector With Built-in Line Isolator

855PC 3oTec Triple Sensor Detector With Built-in Line Isolator

855PC 3oTec Triple Sensor Detector With Built-in Line Isolator

855PH Photo Heat Detector With built-in Line Isolator

855PH Photo Heat Detector With built-in Line Isolator