NBS Source
I'm a manufacturer
Compare variants

7340 Metering Station

Verified by manufacturer 6 months ago

DN50

Victaulic Variant:
Third party certifications:
  • ISO 9001 Quality Management

    Certificate type

A grooved end metering station for HVAC systems.

Jump to:
+44 (0)1438 310690 Website

Application

  • Used to obtain flow measurements in HVAC systems.
  • To obtain an accuracy of +/– 3%, the Series 7340 should be installed in a straight run of pipe having at least five (5) pipe diameters upstream and three (3) pipe diameters downstream free of flow disturbances (i.e., valves, outlets, fittings, etc.).
  • When the Series 7340 is close coupled to a globe-style or butterfly balancing valve, five (5) straight pipe diameters upstream of the valve is required to obtain +/-5% accuracy.
  • Install the Series 7340 with two (2) Style 107N Installation-Ready™ rigid couplings.

Description

A grooved end metering station for HVAC systems.


Features and benefits:

  • Accurate, economical method for obtaining flow measurements.
  • Maintenance-free design.
  • Sizes from 2–12″ | DN50–DN300.
  • Accommodates pressures ranging from full vacuum (29.9 in Hg/760 mm Hg) up to 750 psi/5171 kPa.
  • All sizes fitted with two (2) extended pressure test ports (marked red upstream and blue downstream). 

General information

Color

Silver

Material

Steel

Nickel

Shape

Other

Length

80 mm

100 mm

Width

95 mm

108 mm

125 mm

147 mm

175 mm

Show more

Manufacturer guidance

Diameter (excluding extended pressure test ports).

Height

95 mm

108 mm

125 mm

147 mm

175 mm

Show more

Manufacturer guidance

Diameter (excluding extended pressure test ports).

Material

Steel

Nickel

Uniclass

Pr_65_54_93_52 Metering stationsPrimary
Pr_65_54_95_30 Flow-measuring valves

Specification data - Metering stations

Manufacturer

Victaulic.

Product reference

7340 Metering Station.

Accessories

Style 107N Installation-Ready™ rigid couplings.

Material

EN1A nickel plated steel (BS230M07).

Connections

Compression.

Operating temperature range

–34ºC to +121ºC ( –30ºF to +250ºF).

Inlets/outlets diameter

DN50.

Weight

1.2 kg.

Flow capacity

55/48 Cv/Kv.

Sustainability data

Material

Steel

Nickel

Third party certifications

ISO 9001 Quality Management

ISO 9001 Quality Management

ISO Certificate

Literature

Victaulic Grooved End Metering Station – Orifice Type

Victaulic Grooved End Metering Station – Orifice Type