NBS Source
I'm a manufacturer

4 Hour Smoke and Fire Curtain To BS EN 1634 - HFS Plus - Fire Curtain

Verified by manufacturer 4 days ago

HAG Ltd. - The Door Specialists Third party certifications:
  • Alcumus SafeContractor

    Alcumus SafeContractor

    Certificate type

  • Constructionline

    Constructionline

    Certificate type

  • dhf certificate

    dhf certificate

    Certificate type

  • Certifire Certificate

    Certifire Certificate

    Certificate type

  • UK Conformity Assessed (UKCA)

    UK Conformity Assessed (UKCA)

    Certificate type

  • DoP

    DoP

    Certificate type

  • Warringtonfire

    Warringtonfire

    Certificate type

  • ADSA

    ADSA

    Certificate type

  • AkzoNobel

    Certificate type

  • Made in Britain

    Made in Britain

    Certificate type

  • CHAS

    CHAS

    Certificate type

  • ISO 9001 Quality Management

    Certificate type

  • CE Marking

    Certificate type

Smoke and fire curtain Integrity (E) 240 mins & (W) 60 minutes irradiance, CERTIFIRE approved. Tested & certified to BS EN 16034.

Jump to:
BOS
0800 072 3444 Website

Application

Smoke and fire curtain suitable for industrial, commercial, residential, public buildings, hospitality and cultural or historical settings

  • Airports
  • Train stations
  • Kitchen servery hatches
  • Retail units
  • Shopping malls
  • Offices
  • Leisure complex
  • Warehouse
  • Factories
  • Chemical plant
  • Hospitals
  • Care homes
  • Receptions areas
  • Schools
  • Colleges
  • Academies
  • Universities
  • Nurseries
  • Residential - high rise or large houses
  • Hotels
  • Restaurants
  • Museums
  • Libraries
  • Historical sites


Description

Smoke and fire curtain providing optimum levels of smoke and fire protection up to 240 minutes with added irradiance shield up to 60 minutes.


Features and benefits:

  • Self-closing.
  • Designed to provide safe evacuation routes in proximity to the fire curtain and protection for close contact.
  • Comes complete with smoke seals as standard to provide up to 240 minutes of smoke and fire protection.
  • CERTIFIRE approved.


Standards:

  • Compliant to EN1634- 1.
  • Compliant to EN 1634-3.
  • Compliant with BS EN 16034:2014.
  • Full CE & UKCA compliance (conformity certificates on request).
  • Complies to Document Part M Building Regulations 2004.
  • Fire integrity (E): Up to 240 minutes.
  • Irradiance (W): 60 minutes.

General information

Color

Grey

Guidance for specification option:

Curtain.

Other

Guidance for specification option:

Head box, guides and bottom rail only.

Finish

Galvanized

Guidance for specification option:

Standard.

Powder-coated

Guidance for specification option:

Optional; insert RAL or BS 4800 colour requirement.

Material

Stainless steel

Fiber-glass

Manufacturer guidance

  • Curtain is manufactured from a woven fibreglass and stainless steel fabric with a coating of intumescent silicone.
  • Box and rails are galvanized steel.

Shape

Rectangle

Length

Bespoke

Manufacturer guidance

Consult manufacturer for options and insert requirements.

Width

Bespoke

Manufacturer guidance

Consult manufacturer for options and insert requirements.

Height

Bespoke

Warranty description

One year

Guidance for specification option:

Comprehensive warranty.

Uniclass

Pr_25_80_79_94 Vertical active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Product range

Fire Protection

Specification data - Vertical active fire curtain barriers

Standards

Guidance for specification option:

See product description or manufacturer's literature for details.

Test standards

Vertical, horizontal and angled to BS EN 1634-1.

Third-party certification

CERTIFIRE certified.

Size

-

Manufacturer guidance

Consult manufacturer for options and insert requirements.

Performance

-

Fire resistance

Up to 240 minutes.

Barrier units

Single, charcoal.

Single, silver grey.

Manufacturer guidance

  • Woven fibreglass and stainless steel fabric with intumescent silicone coating.
  • Smoke seals included as standard.

Deployment

Split drop.

Delayed drop.

Manufacturer guidance

The system is held in the open position by a single phase electric 24 V d.c. motor. When a fire is detected or power is lost the motor will disengage and allow the gravity failsafe to activate.

Activation

Guidance for specification option:

Manufacturer's standard.

Accessories

None.

Vision panels.

Guidance for specification option:

  • Silicone optical resin rescue vision windows that allow emergency services to see into the area for rescue purposes.
  • 270 x 400 mm each, certified to 240 minutes' fire protection.

Audio/ visual warning devices.

Emergency retract switches.

Beam sensors.

Fixing

Face.

Reveal.

Other.

Guidance for specification option:

Can be installed in suspended or solid ceilings.

Frame and guides

Galvanized.

Guidance for specification option:

Standard.

Polyester powder-coated, colour.

Guidance for specification option:

Insert requirements to any standard RAL or BS 4800 colour.

Manufacturer guidance

All components are formed from galvanized steel.

Box:

The curtain assembly comprises a box housing which includes the motorized barrel and wrapped curtain. The box is attached to channel section guides at each end – these guides are the main fixing point for the entire system.

Guide rails:

100 x 50 mm.

Head box:

  • Up to 4000 mm high: 180 x 180 mm.
  • Over 4000 mm: 210 x 210 mm.

Bottom rail:

Industry-standard ‘bell’.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Material

Stainless steel

Fiber-glass

Manufacturer guidance

  • Curtain is manufactured from a woven fibreglass and stainless steel fabric with a coating of intumescent silicone.
  • Box and rails are galvanized steel.

Recyclability

Yes

Manufacturer guidance

90%

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

15 %

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

IFC
-

1

Third party certifications

Alcumus SafeContractor

Alcumus Safe Contractor Certificate of Accreditation

Constructionline

Construction Line Gold Membership

dhf certificate

DHF Full Member

Certifire Certificate

Warrington Fire - Certifire

Alcumus SafeContractor

Alcumus SafeContractor

UK Conformity Assessed (UKCA)

UK Conformity Assessed (UKCA)

Alcumus SafeContractor

SAFE PQQ Alcumus Safe Contractor

DoP

Certificate of Constancy of Performance (Fire)

Warringtonfire

Certificate of Constancy of Performance

ADSA

ADSA Membership

AkzoNobel

Akzo Nobel Power coated

Made in Britain

Builders Profile Membership

CHAS

CHAS Certificate of Accreditation

Made in Britain

Environment Agency Waste Management Certificate

ISO 9001 Quality Management

ISO 9001

DoP

BS EN 16034:2014

CE Marking

CE Marking

Literature

Fireguard HFS Plus

Fireguard HFS Plus

CAD HFS Plus

CAD HFS Plus

Case studies

Jaguar Land Rover

Jaguar Land Rover

Heathrow Terminal 5

Heathrow Terminal 5

Similar products from HAG Ltd. - The Door Specialists

3 Hour Fire Curtain To BS 8524-1 - Fireguard XR180 - Fire Curtain

3 Hour Fire Curtain To BS 8524-1 - Fireguard XR180 - Fire Curtain

3 Hour Smoke and Fire Curtain To BS 8524-1 - XR Plus - Smoke and Fire Curtain

3 Hour Smoke and Fire Curtain To BS 8524-1 - XR Plus - Smoke and Fire Curtain

4 Hour Fire Curtain - HF240 To BS EN 1634 - Fire Curtain

4 Hour Fire Curtain - HF240 To BS EN 1634 - Fire Curtain