Fire curtain with Integrity (E) of 240 minutes and Irradiance (W) of 60 minutes, CERTIFIRE approved. Tested and certified to BS EN 16034 standards.

Jump to:
BOS
0800 072 3444 Website

Application

Fire curtain suitable for internal industrial, commercial, residential, public buildings, hospitality and cultural or historical settings.

  • Airports
  • Train stations
  • Kitchen servery hatches
  • Retail units
  • Shopping malls
  • Offices
  • Leisure complex
  • Warehouse
  • Factories
  • Chemical plant
  • Hospitals
  • Care homes
  • Receptions areas
  • Schools
  • Colleges
  • Academies
  • Universities
  • Nurseries
  • Residential - high rise or large houses
  • Hotels
  • Restaurants
  • Museums
  • Libraries
  • Historical sites


Description

Premium fire-resistant curtain providing up to 240 minutes of fire protection, with the added benefit of 60 minutes of irradiance shielding (depending on size).

Features and benefits:

  • Unlimited widths can be obtained by overlapping curtains. 
  • Self-closing.
  • Can be installed in suspended or solid ceilings. It can be face or reveal fixed to steel and masonry.

Standards:

  • Tested and compliant to BS EN 1634.
  • Compliant with BS EN 16034:2014.
  • Fire Integrity (E) of up to 240 minutes.
  • Radiation Performance (EW60) 60 minutes.
  • Full CE Compliance (conformity certificates on request).
  • Tested and compliant to the latest European standards BS EN 1634.
  • Complies to Document Part M Building Regulations 2004.
  • CERTIFIRE Certified.

General information

Color

Grey

Guidance for specification option:

Curtain.

Other

Finish

Galvanized

Guidance for specification option:

Head box, guides and bottom rail only.

Powder-coated

Guidance for specification option:

  • Polyester powder-coated (PPC).
  • Head box, guides and bottom rail only.

Material

Stainless steel

Fiber-glass

Manufacturer guidance

  • Curtain is manufactured from a woven fibreglass and stainless steel fabric with a coating of intumescent silicone.
  • Box and rails are galvanized steel.

Shape

Rectangle

Width

20000 mm

Manufacturer guidance

Maximum width.

Height

6000 mm

Manufacturer guidance

Maximum height.

Warranty description

One year

Guidance for specification option:

Comprehensive warranty.

Uniclass

Pr_25_80_79_94 Vertical active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Product range

Fire Protection

Specification data - Vertical active fire curtain barriers

Standards

Tested and compliant to the latest European standards BS EN 1634.

Third-party certification

CERTIFIRE certified.

Size

-

Manufacturer guidance

Insert requirements. Multiple sections can be overlapped to maximum width of 20 000 mm and a maximum height of 6000 mm.

Performance

-

Fire resistance

Up to 240 minutes.

Barrier units

Single, charcoal.

Single, silver grey.

Manufacturer guidance

Woven fibreglass and stainless steel fabric with intumescent silicone coating.

Deployment

Split drop.

Delayed drop.

Manufacturer guidance

The system is held in the open position by a single phase electric 24 V d.c. motor. When a fire is detected or power is lost the motor will disengage and allow the gravity failsafe to activate.

Activation

Fire/ smoke alarm signal.

Accessories

None.

Beam sensors.

Emergency retract switches.

Audio/ visual warning devices.

Fixing

Face.

Reveal.

Other.

Guidance for specification option:

Can be installed in suspended or solid ceilings.

Frame and guides

Galvanized.

Guidance for specification option:

Standard.

Polyester powder-coated, colour.

Guidance for specification option:

Insert requirements to any standard RAL or BS4800 colour.

Manufacturer guidance

All components are formed from galvanized steel.

Box:

The curtain assembly comprises a box housing which includes the motorized barrel and wrapped curtain. The box is attached to channel section guides at each end – these guides are the main fixing point for the entire system.

Guide rails:

100 x 50 mm.

Head box:

  • Up to 4000 mm high: 180 x 180 mm.
  • Over 4000 mm: 210 x 210 mm.

Bottom rail:

Industry-standard ‘bell’.

Radiation

60 minutes.

Dimensions

Guidance for specification option:

Insert requirements, maximum width 20 m; maximum height 6 m.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Material

Stainless steel

Fiber-glass

Manufacturer guidance

  • Curtain is manufactured from a woven fibreglass and stainless steel fabric with a coating of intumescent silicone.
  • Box and rails are galvanized steel.

Recyclability

40

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

15 %

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

IFC
-

1

Third party certifications

AkzoNobel

Akzo Nobel Power coated

Alcumus SafeContractor

Alcumus Safe Contractor Certificate of Accreditation

CHAS

CHAS Certificate of Accreditation

Constructionline

Construction Line Gold Membership

dhf certificate

DHF Full Member

ISO 9001 Quality Management

ISO 9001

Certifire Certificate

Warrington Fire - Certifire

Alcumus SafeContractor

Alcumus SafeContractor

DoP

Certificate of Constancy of Performance (Fire)

UK Conformity Assessed (UKCA)

UK Conformity Assessed (UKCA)

Warringtonfire

Certificate of Constancy of Performance

DoP

BS EN 16034:2014

Literature

Fireguard HF240

Fireguard HF240

CAD HF240

CAD HF240

Similar products from HAG Ltd. - The Door Specialists

3 Hour Smoke and Fire Curtain To BS 8524-1 - XR Plus - Smoke and Fire Curtain

3 Hour Smoke and Fire Curtain To BS 8524-1 - XR Plus - Smoke and Fire Curtain

3-hour fire curtain, tested to BS 8524-1 standards – Fireguard XR180 - Fire Curtain

3-hour fire curtain, tested to BS 8524-1 standards – Fireguard XR180 - Fire Curtain

4 Hour Smoke and Fire Curtain To BS EN 1634 - HFS Plus - Fire Curtain

4 Hour Smoke and Fire Curtain To BS EN 1634 - HFS Plus - Fire Curtain