Newton High Water Alarm

Application

Provides an alarm function for single or twin pump systems where no control panel is installed.

Description

The Newton High Level Water Alarm (PA50) has been designed to detect high water levels within pump sump chambers, and is included within the Newton Titan-Pro and Newton Titan pumping systems. The alarm is powered by a standard 9V PP3 battery.

It can be programmed to automatic reset or manual reset after an alarm occurrence. A mute button to the front face silences the alarm once the alarm condition is discovered. A flashing alarm light gives visual indication of an alarm condition, and this light will continue to show even when the alarm sounder is muted.

When the unit is to be used within a single pump system, the alarm switch should be positioned just above the point where the single pump should start pumping. When used within a twin pump system, the switch should be set at a height above the point of the start of the lower pump but below the point where the secondary pump would ordinarily start.


Features and benefits:

  • The alarm sound reaches 90 dB.
  • Includes auto or manual reset options.
  • Can be either surface mounted or flush mounted to a standard electric black box.
  • Includes a 5 m float cable, and mute and test buttons.
  • Zero voltage output is used to notify the Newton Text and Speech Dialer or BMS (Building Management System) of an alarm occurrence.

General information

Color

Blue

Size

152 x 92 x 37 mm (8.00 mm if mounted in back box) (w x h x depth)

WarrantyDescription

The alarm is supplied with a one-year back-to-base warranty which is dated from either the date of purchase or a proven date of installation. If the unit develops a fault during the warranty period, Newton Waterproofing Systems will repair or replace the unit under warranty. Consult manufacturer for a returns form which explains the returns procedure. The warranty will be invalidated if the unit is damaged because of improper handling, storage, or installation and in such cases a repair charge may be applicable

Uniclass 2015

Pr_70_55_76_62 Private packaged pumping stationsPrimary

CAWS

J40/290 High density polyethylene/ polypropylene studded cavity drain membrane

R12/135 Private packaged pumping stations and pressure pipeline system

R18/310 Private packaged pumping stations

Product range

Pumps, Pumping Stations and Ancillaries / Pump Control, Monitoring and Alarms

Specification data - Private packaged pumping stations Enhanced data

Collection tank

-

Configuration

Single pump system.

the alarm switch should be positioned just above the point where the single pump should start pumping.

Twin pump system.

the switch should be set at a height above the point of the start of the lower pump but below the point where the secondary pump would ordinarily start

Pumps

-

Pump characteristic

High Water Alarm which is included within the Newton Titan-Pro and Newton Titan pumping systems.

Control

Provides alarm function for single or twin pump systems where no control panel is installed.

Integral accessories

Newton text and speech Dialer (PA5).

Product Reference

Newton High Water Alarm (PA50)

Weight

700 g.

Power supply

9 V.

PP3 battery (supplied).

Sounder volume (dB)

90 dB.

at 1000 mm

Switching

Reed switch.

Literature

Newton High Water Alarm

Newton High Water Alarm

Similar products from Newton Waterproofing Systems

DAB E.Box

DAB E.Box

Newton Control Panel-Pro

Newton Control Panel-Pro

Newton NP Effluent Water Pumps

Newton NP Effluent Water Pumps

Newton Pump Controller

Newton Pump Controller

Newton SP750 Cutter Sewage Pump

Newton SP750 Cutter Sewage Pump

Newton Titan-2 - Compact Packaged Pumping System

Newton Titan-2 - Compact Packaged Pumping System

Newton Titan-Pro – Packaged Pumping System

Newton Titan-Pro – Packaged Pumping System

Newton Trojan-Pro

Newton Trojan-Pro

Universal Wall Entry - UDME100/300

Universal Wall Entry - UDME100/300