Ringmaster AirSeT - Ring Main Unit
Ringmaster AirSeT - Ring Main Unit
Ringmaster AirSeT - Ring Main Unit

Verified 4 days ago

Schneider Electric Ltd

Verified 4 days ago

Schneider Electric Ltd

Verified 4 days ago

Schneider Electric Ltd
Summary
Ring main units with two ring switch disconnectors and circuit breaker.
-
-
Application

Ringmaster AirSeT design is the optimal choice for electrical distribution companies and distribution services, suitable for the following applications:

  • Building and industries.
  • Energy and infrastructure.
  • Mining.
  • Package substation.
-
-
Description

Non-extensible (RN2Air) ring main units with two ring switch disconnectors and circuit breaker in pure air gas filled tank with pressure relief facility.

Features and benefits:

  • IP54 degree of protection of the Ringmaster’s enclosure instead of housing makes it possible to be used in the most aggressive environment.
  • No consideration needs to be taken for an external enclosure, saving cost compared to traditional solutions.
-
-
Color
Grey
-
-
Finish
Smooth
-
-
Material
Metal
-
-
Shape
Rectangle
-
-
Length
1019 mm
-
-
Width
866 mm
-
-
Height
1800 mm
-
-
SKU Code
RN2Air-T2 VIP400
-
-

Specification

Classification data
Standard
To IEC 62271-1, IEC 62271-200 and IEC 62271-201.
-
-
Third-party certification
To ENA TS 41-41.
-
-
Internal arc classification
To IEC 62271-200, Class AF.
-
-
Mounting arrangement
Transformer-mounted., Free-standing.
-
-
Switchgear arrangement
Non-extensible.
-
-
Rated voltage (Ur)
12 kV.
-
-
Rated frequency
50 Hz.
-
-
Number of phases
Three.
-
-
Rated insulation levels
-
-
-
Rated short-duration power frequency withstand voltage (Ud)
28 kV for one minute., 38 kV for one minute.
-
-
Rated lightning impulse withstand voltage (Up)
75 kV phase-to-phase, phase-to-earth., 95 kV phase-to-phase, phase-to-earth.
-
-
Rated short-time withstand current (Ik)
21 kA for three seconds.
-
-
Enclosure
-
-
-
Ingress protection (minimum)
To BS EN 60529, IP54.
-
-
Mechanical protection (minimum)
IK10.
-
-
Colour
Grey.
-
-
Cable entry
Direct coupling to transformer., Free-standing.
-
-
Dimensions
-
-
-
Width (maximum)
890 mm.
-
-
Height (maximum)
1810 mm.
-
-
Depth (maximum)
920 mm.
-
-
Busbars
-
-
-
Material
Bare copper.
-
-
Rated continuous current (Ir)
200 A., 630 A.
-
-
Ring switches
-
-
-
Standard
To IEC 62271-102 and IEC 62271-103.
-
-
Format
SF6-free, circuit breaker earth switch.
-
-
Rated continuous current (Ir)
630 A.
-
-
Rated short circuit making current (Ima)
52.5 kA.
-
-
Switch class
E2.
-
-
Operating mechanism
Independent manual., Motor operated.
-
-
Circuit breaker
-
-
-
Standard
To IEC 62271-100.
-
-
Format
SF6-free, circuit breaker earth switch.
-
-
Method of installation
Fixed.
-
-
Rated continuous current (Ir)
200 A.
-
-
Rated short circuit breaking current (Isc)
21 kA.
-
-
Rated short circuit making current (Ima)
52.25 kA.
-
-
Rated operating sequence
O – 3 min – CO – 3 min – CO.
-
-
Circuit breaker class
E2.
-
-
Operating mechanism
Independent manual., Motor operated.
-
-

Additional properties

Protection
VIP400 Relay.
-
-
Indication
Pure air gauge, mechanism ON/OFF, mechanism EARTH/MAIN, on-off push button.
-
-
Model
RN2Air-T2 VIP400.
-
-

Sustainability data

Material
Metal
-
-