A1S Flameshield Overlapping Fire Curtain 8524 - Fire Curtain
A1S Flameshield Overlapping Fire Curtain 8524 - Fire Curtain

Verified 5 days ago

A1S Group

1634 - No Smoke Seals

Verified 5 days ago

A1S Group

8524 - No Smoke Seals

Summary
Overlapping vertical fire curtain barrier.
Overlapping vertical fire curtain barrier.
Material
Carbon steel
Carbon steel
Shape
Rectangle
Rectangle
Length
Bespoke
Bespoke
Width
Bespoke
Bespoke
Height
Bespoke
Bespoke

Specification

Standards
To BS 8524-1, BS EN 1634-1, BS 476-6 and -7, BS EN 12605, BS EN 14600, BS EN 13501-2 and BS EN 16034.
To BS 8524-1, BS EN 1634-1, BS 476-6 and -7, BS EN 12605, BS EN 14600, BS EN 13501-2 and BS EN 16034.
Barrier assemblies
To BS 8524-1.
To BS 8524-1.
Test standards
Vertical, horizontal and angled to BS EN 1634-1.
Vertical, horizontal and angled to BS EN 1634-1.
Third-party certification
Warrington Fire Report 367279.
Warrington Fire Report 367279.
Performance
-
-
Smoke containment
No Smoke Seals.
No Smoke Seals.
Fire resistance
60 minutes., 120 minutes.
60 minutes., 120 minutes.
Accessories
Partial Drop., Emergency Retract., BMS Interface., Obstruction Beam Detection Device., Audio / Visual / Spoken Warning Unit.
Partial Drop., Emergency Retract., BMS Interface., Obstruction Beam Detection Device., Audio / Visual / Spoken Warning Unit.

Additional properties

Radiation
74 minutes at 15 kW/m².
74 minutes at 15 kW/m².
Fabric
Fire curtains are formed from a fire rated fabric 0.54 mm thick stainless steel wire reinforced, with a specially formulated aluminum pigmented and fire retardant polymer which provides a heat reflecting surface as well as other properties for smoke and fire.
Fire curtains are formed from a fire rated fabric 0.54 mm thick stainless steel wire reinforced, with a specially formulated aluminum pigmented and fire retardant polymer which provides a heat reflecting surface as well as other properties for smoke and fire.
Barrel
Fire curtain barrels are manufactured from carbon steel tube, tube size dependent on the overall size of the unit and deflection calculated to conform to British Standards.
Fire curtain barrels are manufactured from carbon steel tube, tube size dependent on the overall size of the unit and deflection calculated to conform to British Standards.

Sustainability data

Material
Carbon steel