FV144 Large Ventilated Cavity Fire Barrier
FV144 Large Ventilated Cavity Fire Barrier
FV144 Large Ventilated Cavity Fire Barrier

Verified 4 months ago

Nullifire – a brand of Tremco CPG UK Ltd

Verified 4 months ago

Nullifire – a brand of Tremco CPG UK Ltd

Verified 4 months ago

Nullifire – a brand of Tremco CPG UK Ltd
Summary
Suited to a ventilated cavity with a maximum air gap of 44 mm and consists of a specially formulated fire rated rock mineral fibre section with an integral high expansion intumescent seal attached.
-
-
Application

Applied horizontally along the compartment line to suit ventilated cavities from 60 mm up to 450 mm, typically with rain screen cladding or similar and will suit most construction types to provide generally up to 180 minutes of integrity and 180 minutes of insulation.


This is possible subject to details, please consult the Nullifire or illbruck Specification Team. Nullifire FV144 is designed to be complimented by Nullifire FJ260 non-ventilated cavity fire barriers applied to the vertical compartment lines.

-
-
Description

Nullifire FV144 ventilated cavity fire barriers are ’open state’ cavity fire barriers for ventilated cavities from 60 mm up to 450 mm.


Each Nullifire FV144 ventilated cavity fire barrier consists of a specially formulated fire-rated stone mineral wool section with an integral high expansion intumescent seal fixed to the leading edge.

The Nullifire FV144 ventilated cavity fire barrier then leaves a maximum 44 mm air gap to allow for drainage and maintain ventilation in normal use. In a fire situation, the intumescent seal rapidly expands to seal off the air gap and prevent vertical fire spread within the external wall.


Nullifire FV144 ventilated cavity fire barrier has undergone extensive fire testing following the principles of ASFP TGD19 (Fire Resistance Test for ‘Open-State’ Cavity Barriers).


Nullifire FV144 ventilated cavity fire barriers are mechanically fixed horizontally within ventilated cavities behind the external wall substrate following the fire compartment line.


Nullifire FV144 ventilated cavity fire barriers are used horizontally and can be installed in conjunction with Nullifire FJ260 Non-Ventilated Fire Barriers which provide vertical fire separation along fire compartment party wall lines.

-
-
Color
Beige, Blue, Grey
-
-
Material
Mineral wool, Stone wool, Polythene, Intumescent
-
-
Shape
Rectangle
-
-
Length
1000 mm
-
-
Width
Bespoke
-
-
Height
75 mm
-
-
Warranty description
Other
-
-

Specification

Classification data
Standard
Tested and certified in accordance with ASFP Technical Guidance Document TDG19.
-
-
Fire performance
Fire-rated for up to 180 minutes.
-
-
Material
Mineral stone wool, polythene sleeve and intumescent band.
-
-
Thickness
6 mm.
-
-
Cavity width
-
-
-
Air gap
44 mm.
-
-

Additional properties

Length
1000 mm., Other.
-
-
Bond
Stainless steel countersunk head screws, maximum head diameter 11.5 mm, length to suit cavity barrier and substrate. 4 no. screws per linear metre.
-
-
Shape
Rectangle.
-
-
Colour
Stone wool (beige), polythene sleeve (blue), intumescent band (grey).
-
-
Durability
Type X.
-
-
Service temperature
-20°C to + 70°C.
-
-
Life expectancy
≥60 years.
-
-
Installation accessories
Drill.
Drill bit and driver.
Appropriate self-tapping screws/fasteners.
Tape measure.
Levelling device.
Saw.
-
-
Execution
-
-
-

Sustainability data

Country of material origin
United Kingdom
-
-
Country of product manufacture
United Kingdom
-
-
Material
Mineral wool, Stone wool, Polythene, Intumescent
-
-