To DIN VDE 0100-710, DIN VDE 0100-718, ÖVE/ÖNORM E 8007, IEC 60364-7-710, DIN EN 61508-1, IEC 61508-1, DIN EN 61508-2, IEC 61508-2, DIN EN 61508-3, IEC 61508-3, DIN EN 60947-6-1, IEC 60947-6-1.
-
-
Method of controlling transfer
Automatic.
-
-
Operating sequence
I-O-II.
-
-
Rated operational voltage (Ue)
230 V.
-
-
Rated insulation voltage (Ui)
250 V.
-
-
Rated operational current (Ie)
63 A.
-
-
Rated operational frequency
50 Hz, 60 Hz.
-
-
Number of poles
Two.
-
-
Terminals
Screw-type terminals.
-
-
Controls
-
-
-
Type
Integral to switch.
-
-
Display type
Liquid crystal display (LCD).
-
-
Illuminated display to indicate the following conditions
Line 1: Measured values of mains voltage and frequency; Switch position of the automatic transfer switching device; Line 2: Measured values of mains voltage and frequency; Display of the load in the IT system in %.
-
-
User-adjustable functions
Changeover; Voltage; Current; Relay; Digital input; Data logger; Language; Interface; Clock; Password.
-
-
Features
Autom. changeover test; Manual changeover test; Last changeover test; Generator test; Test communication.
-
-
Enclosure
-
-
-
Ingress protection (minimum)
To DIN EN 60529, IP40.
-
-
Material
Polycarbonate.
-
-
Colour
Yellow.
-
-
Additional properties
Accessories
ATICS-BP-2-63A-SET Bypass switch set.
-
-
Sustainability data
Country of product manufacture
Germany
-
-
Material
Polycarbonate
-
-
Recyclability
Can be returned to manufacturer for disposal under WEEE regulations.