NBS Source
I'm a manufacturer

Compare variants

Kingspan KoolDuct System - Pre-insulated HVAC Ductwork System
Kingspan KoolDuct System - Pre-insulated HVAC Ductwork System

Verified 7 months ago

Kingspan Insulation

Kingspan KoolDuct System - 22 mm

Verified 7 months ago

Kingspan Insulation

Kingspan KoolDuct System - 30 mm

Summary
Energy efficient, lightweight pre-insulated rectangular HVAC ductwork system with low air leakage. Fabricated with premium performance Kingspan KoolDuct® phenolic panels.
Energy efficient, lightweight pre-insulated rectangular HVAC ductwork system with low air leakage. Fabricated with premium performance Kingspan KoolDuct® phenolic panels.
Third party certification
Digital objects
Color
Grey, Pink
Grey, Pink
Finish
Foil
Foil
Material
Phenolic foam
Phenolic foam
Shape
Other
Other
Length
2950 mm
2950 mm
Width
1200 mm
1200 mm
Height
22 mm, 30 mm
22 mm, 30 mm

Specification

Standard
To BS EN 13403.
To BS EN 13403.
Insulation material
Phenolic foam (PF).
Phenolic foam (PF).
Internal and external material
Phenolic insulation is covered by factory-applied aluminium foil facings on both sides.
Phenolic insulation is covered by factory-applied aluminium foil facings on both sides.
Finish
Aluminium foil facing.
Aluminium foil facing.
Accessories
-
-
Material
Compatible with ductwork.
Compatible with ductwork.
Finish
Aluminium foil facing.
Aluminium foil facing.
Access openings
-
-
Purpose
Inspection.
Inspection.
Sizes
To BS EN 12097.
To BS EN 12097.
Execution
Air ductwork generally.
Air ductwork generally.

Additional properties

ThermalConductivity
0.023 W/m·K at -20°C, 0.022 W/m·K at 10°C, 0.023 W/m·K at 19°C, 0.024 W/m·K at 25°C, 0.027 W/m·K at 50°C, 0.031 W/m·K at 80°C.
0.023 W/m·K at -20°C, 0.022 W/m·K at 10°C, 0.023 W/m·K at 19°C, 0.024 W/m·K at 25°C, 0.027 W/m·K at 50°C, 0.031 W/m·K at 80°C.
Standard
BS EN ISO 9001: 2015 (Quality Management Systems. Requirements), BS EN ISO 14001: 2015 (Environmental Management Systems. Requirements), BS ISO 45001: 2018 (Occupational health and safety management systems) and
BS EN ISO 50001: 2018 (Energy management systems. Requirements with guidance for use), BS EN 14314:2009+A1:2013
BS EN ISO 9001: 2015 (Quality Management Systems. Requirements), BS EN ISO 14001: 2015 (Environmental Management Systems. Requirements), BS ISO 45001: 2018 (Occupational health and safety management systems) and
BS EN ISO 50001: 2018 (Energy management systems. Requirements with guidance for use), BS EN 14314:2009+A1:2013
Insulation thickness (minimum)
22 mm.
30 mm.
Vapour barrier material
Factory-applied aluminium foil (standard for indoor use) vapour .barrier facing
Factory-applied aluminium foil (standard for indoor use) vapour .barrier facing
Protection
If the duct system is to the external of the building it has to be protected by one of the following: aluminium sheet, aluminium–zinc alloy coated steel sheet, heavy-duty self-adhesive laminate, reinforcing glass/ synthetic cloth embedded between two coats of appropriate coating or UV resistant glass reinforced polyester/ epoxy (GRP/ GRE).
If the duct system is to the external of the building it has to be protected by one of the following: aluminium sheet, aluminium–zinc alloy coated steel sheet, heavy-duty self-adhesive laminate, reinforcing glass/ synthetic cloth embedded between two coats of appropriate coating or UV resistant glass reinforced polyester/ epoxy (GRP/ GRE).
Accessories
For duct assembly: Either tiger clips or adhesive, aluminium foil tape and silicone sealant. Flanges/ couplings: tiger clips or 4-bolt flange/ aluminium grip flange with bayonet cleat. Reinforcements / stiffners: Tie rods/Reinforcing bars.
For duct assembly: Either tiger clips or adhesive, aluminium foil tape and silicone sealant. Flanges/ couplings: tiger clips or 4-bolt flange/ aluminium grip flange with bayonet cleat. Reinforcements / stiffners: Tie rods/Reinforcing bars.
Reaction to fire classification
Euroclass B-s2,d0 both sides.
Euroclass B-s1,d0 exposed foil side and C-s2,d0 non-exposed foil side.
FM approved
No (not applicable to pre-insulated ductwork for HVAC application).
No (not applicable to pre-insulated ductwork for HVAC application).
Compressive strength (minimum)
>175 kPa at 10% compression.
>175 kPa at 10% compression.
Closed cell content
≥90%.
≥90%.
Nominal density range
55–60 kg/m³.
55–60 kg/m³.

Sustainability data

Country of material origin
United Kingdom
United Kingdom
Country of product manufacture
United Kingdom
United Kingdom
Embodied carbon
3.36 kg CO₂ eq/kg
3.36 kg CO₂ eq/kg
Recycled content
0 %
0 %