NBS Source
I'm a manufacturer

Compare variants

XT Moulded Case Breakers - Tmax XT Moulded Case Circuit Breakers
XT Moulded Case Breakers - Tmax XT Moulded Case Circuit Breakers
XT Moulded Case Breakers - Tmax XT Moulded Case Circuit Breakers

Verified 2 days ago

ABB Ltd

Verified 2 days ago

ABB Ltd

Verified 2 days ago

ABB Ltd
Summary
Tmax XT moulded case circuit breakers guarantee an extremely high performance level while being progressively smaller in size, simple to install and able to provide increasingly better safety.
Color
Grey
-
-
Material
Metal, Plastic
-
-
Shape
Rectangle
-
-
Length
70 mm, 82.5 mm, 145 mm, 103.5 mm, 166 mm, 178 mm
-
-
Width
76.2 mm, 101.6 mm, 120 mm, 140 mm, 105 mm, 186 mm, 210 mm, 280 mm
-
-
Height
130 mm, 150 mm, 160 mm, 205 mm, 268 mm
-
-
Warranty description
One year
-
-

Specification

Standards
To IEC 60947-2.
-
-
Third-party certification
Declaration of Conformity - CE; GL certificate; LR certificate.
-
-
Rated operational current (Ie)
160 A.
-
-
Number of poles
Three.
-
-
Rated operational voltage (Ue)
690 V a.c./ 500 V d.c.
-
-
Rated insulation voltage (Ui)
800 V.
-
-
Rated impulse withstand voltage (Uimp)
8 kV.
-
-
Rated frequency
50 Hz., 60 Hz.
-
-
Rated ultimate short circuit breaking capacity (Icu)
100 kA (220/ 230/ 240 V a.c.); 70 kA (380/ 415 V a.c.); 65 kA (440 V a.c.); 50 kA (500 V a.c.); 35 kA (525 V a.c.); 10 kA (690 V a.c.); 70 kA (250 V d.c. two poles in series; 500 V d.c. three poles in series).
-
-
Rated service short circuit breaking capacity (Ics)
80 kA (220/ 230/ 240 V a.c.); 52.5 kA (380 V a.c.); 37.5 kA (415 V a.c.); 32.5 kA (440 V a.c.); 25 kA (500 V a.c.); 17.5 kA (525 V a.c.); 5 kA (690 V a.c.); 52.5 kA (250 V d.c. two poles in series; 500 V d.c. three poles in series).
-
-
Utilization category
Manufacturer's standard.
-
-
Protection
-
-
-
Type
Thermal/ magnetic.
-
-
Characteristics
Manufacturer's standard.
-
-
Settings
Setting range: 160/ 136/ 112 A.
-
-
Measurement
Manufacturer's standard.
-
-
Adjustment
Rotary dials.
-
-
Suitable for isolation
Required.
-
-
Method of installation
Manufacturer's standard.
-
-
Service conditions
Manufacturer's standard.
-
-
Ingress protection (minimum)
Manufacturer's standard.
-
-
Connections
-
-
-
Position
Front.
-
-
Configuration
Bolt.
-
-
Accessories
-
-
-

Additional properties

Net weight
1.1 kg.
-
-
Durability
Electrical: 120 cycles per hour; 8000 cycle.
Mechanical: 240 cycles per hour; 25 000 cycle.
-
-
Rated instantaneous short-circuit current setting (Ii)
1600 A.
-
-
Opening
Circuit breaker with SOR/ UVR: 15 ms.
-
-
ConnectionSubtype
XT1.
-
-

Sustainability data

Country of product manufacture
Italy
-
-
Material
Metal, Plastic
-
-
Embodied carbon
9.1 kg CO₂ eq/unit
-
-