NBS Source
I'm a manufacturer

Compare variants

Medipower™ Double Cabinet IPS+IFS+BATS  - Medical IT Power Supply
Medipower™ Double Cabinet IPS+IFS+BATS  - Medical IT Power Supply
Medipower™ Double Cabinet IPS+IFS+BATS  - Medical IT Power Supply

Verified 1 month ago

Brandon Medical Co Ltd

Verified 1 month ago

Brandon Medical Co Ltd

Verified 1 month ago

Brandon Medical Co Ltd
Summary
Isolated power supply for group 2 medical locations.
Digital objects
-
-
Color
Grey
-
-
Finish
Powder-coated
-
-
Material
Steel
-
-
Shape
Rectangle
-
-
Length
350 mm
-
-
Width
550 mm
-
-
Height
2000 mm
-
-

Specification

Standards
To HD60364-7-710, group 2. To HTM06-01, category 5 areas.
-
-
Accessories
Not required., Pass switch., Surge protection., MCB tripped monitoring., Network gateway., MODbus interface., Primary side outgoing RCBO’s (Type – 2C,25)., BATS external by pass.
-
-

Additional properties

Configuration
Double cabinet.
-
-
Components
Incoming isolator.
Insulation fault system - IFS.
Control and monitoring device - UEI.
Motorized actuators, disconnect switches and auxiliary contacts.
-
-
Dimensions
2000 x 550 x 350 mm.
-
-
Enclosure
Mild steel, RAL 7035.
-
-
Mounting
Floor., Wall.
-
-
Fans
2.
-
-
Air flow
42 m³/hr per IPS channel.
-
-
Ingress protection (IP) rating
IP41.
-
-
Protective earth bars
100 A.
-
-
Circuit breakers
18.
-
-
Transformers
4 kVA.
-
-
Rated frequency
50–60 Hz.
-
-
Input voltage
230 V AC.
-
-
Current rating
17.4 A.
-
-
Power dissipation
Heat power dissipation no-load: <36 W.
Heat power dissipation 100%-load: <138 W.
-
-
Efficiency
96%.
-
-
Weight
52 kg.
-
-
Supply
Typical MCB Supply (A): C32 or D25.
Typical MCCB Supply (A): AF63/ AT30.
-
-

Sustainability data

Country of product manufacture
United Kingdom
-
-