Siderise CW-FS firestop & CW-CB cavity barrier systems offer an extensive range of solutions for fire-stopping, horizontal perimeter seals, and acoustic barrier requirements in all curtain wall applications. CW systems may also be used in firestop and cavity barrier applications in conjunction with weathertight façade systems such as precast concrete cladding, composite & architectural cladding panels.
The primary function of the CW system is to maintain continuity of fire resistance by sealing the void between the compartment floors or walls and the external curtain wall both horizontally and vertically.
CW systems’ unique product construction also provides the ability to accommodate movement for the products expected service lifespan of 60 years.
Siderise CW systems are manufactured using a method that provides resilient lateral compression. This facilitates installation, ensuring the requisite tight fit and enhancing the fire integrity of the product.
Throughout the range, the materials comprise a one-piece product with a pre-compressed non-combustible stone wool core. The products also have integral aluminium foil facings to provide an overall Class A1 rating (to BS EN 13501-1:2018 “Fire classification of construction products and building elements.”).
The systems can offer tested fire resistance options ranging from 30 mins to 3 hours (3 hours to BS EN 1364-4:2014 “Fire resistance tests for non-loadbearing elements.” only) and can accommodate void widths up to 400mm. In addition to providing an effective seal against the passage of fire, the products are also acoustically absorptive.
Features and Benefits:
Certified
Certified
Certified