NBS Source
I'm a manufacturer

Compare variants

UE - humiSteam - Steam Humidifier Range
UE - humiSteam - Steam Humidifier Range
UE - humiSteam - Steam Humidifier Range

Verified 4 months ago

CAREL

Verified 4 months ago

CAREL

Verified 4 months ago

CAREL
Summary
Immersed electrode humidifiers which are designed to generate safe steam humidification for duct, in-room, or steam bath application.
Third party certification
Digital objects
-
-
Color
Silver
-
-
Finish
Galvanized
-
-
Material
Metal
-
-
Shape
Rectangle
-
-
Length
365 mm, 545 mm, 635 mm, 1150 mm
-
-
Width
275 mm, 375 mm, 465 mm
-
-
Height
712 mm, 815 mm, 890 mm
-
-
Warranty description
Two year
-
-

Specification

Electrical supply type
Three phase, 208 V a.c., 50/ 60 Hz (W)., Three phase, 230 V a.c., 50/ 60 Hz (K)., Three phase, 400 V a.c., 50/ 60 Hz (L)., Three phase, 460 V a.c., 50/ 60 Hz (M)., Three phase, 575 V a.c., 50/ 60 Hz (N).
-
-
Steam source
Electrode boiler (immersed electrodes).
-
-
Material
Galvanized metal housing.
-
-
Access doors for maintenance
Manufacturer's standard.
-
-
Accessories
None., DP/*R0 lance for duct (standard)., DP/*RU lance for duct (high capacity)., DP/*RH lance for duct (high efficiency)., SDP steam nozzle, 12 mm hole., SDP steam nozzle, 22 mm hole., SDP steam nozzle, no hole (to be drilled)., Hoses., Probe - DPW* wall sensor., Probe - DPP* sensor for industrial environments., Probe - DPD* duct sensor., Probe - ASET* temperature sensor for steam baths., Fan blower, VS*., Fan blower, VR*.
-
-

Additional properties

Dimensions
545 x 375 x 815 mm.
-
-
Weight
34 kg.
-
-
Connection
Standard; code 0.
-
-
Network type
Modbus®., BacNET RS485., BacNET Ethernet., Modbus Ethernet., LON., KONNEX.
-
-
Steam
Rated production: 45 kg/h.
-
-
Power consumption
33.75 kW.
-
-
Connections
Steam: 40 mm diameter.
Water fill: 3/4”G male.
Water drain: 40 mm.
-
-
Pressure
Outlet pressure limits: 0–2000 Pa.
-
-
Cylinders
Standard; code 0., Standard cleanable; code C., For low conductivity; code 1., For low conductivity, cleanable; code 2.
-
-
Conditions
Operating: 1 to 40°C, 10–60% relative humidity.
Storage: -10 to 70°C, 5–95% relative humidity.
-
-
Ingress protection
IP20.
-
-
Model
Basic (Y)., X-plus (X).
-
-
Water
Fill:
· Temperature limits: 1 to 40°C.
· Water pressure limits: 0.1 to 0.8 MPa (1 to 8 bar).
· Instant flow rate: 5.85 L/m.
· Total hardness: 10 to 40°fH.
· Conductivity limits: 75 to 1250 μS/cm.
Drain:
· Temperature: <100°C.
· Instant flow rate: 22 L/m.
-
-
Fan
One blower, type VRDXL; rated air flow: 576 m³/h.
-
-
Classification