Monolithic UPS - Uninterruptible Power Supplies
Monolithic UPS - Uninterruptible Power Supplies
Monolithic UPS - Uninterruptible Power Supplies

Verified 5 months ago

Bender UK

Verified 5 months ago

Bender UK

Verified 5 months ago

Bender UK
Summary
Monolithic uninterruptible power supplies.
-
-
Application

Guidance on the use of UPS for medical locations is provided by:

  • British Standards BS7671:2008 (2011).
  • HTM 06-01 2017.
  • ETCI ET101:2008.

The regulations and guidance documents state that for Group 2, Category 4 and 5 medical locations, in the event of a failure the battery system for tertiary power supplies should be able to provide an autonomous supply for a period of at least three hours. If there is a secondary power source available with a 25-second change-over time, this autonomy can be reduced to one hour. The guidance document HTM 06-01 2017, states that the battery system must have a 10 years’ design life, thread insert connections, fire retardant case, and provide 60-minute autonomy.

-
-
Description

Industry standards, including IEC 60364-7-710 and HTM06-01, require that if a hospital’s main power supply fails an alternative should kick-in within 0.5 seconds, at least in areas where isolated power is installed. And for some electronic equipment even this is too long.


Electrical power supplies and IPS systems can have their reliability enhanced with Uninterruptible Power Supplies, ATICs and back-up generators.


UPS systems can be supplied as standalone units or for enhanced resilience, may be configured as N+ 1 solution with single, double or triple input supplies. Isolated Power Supplies configured with ATICs and N+1 UPS systems are often considered the most resilient solutions available.

Alarms and diagnostics from the various elements of the system can be integrated to provide operational reports, predictive forecasts, current and emergency information.


This can be supplied directly to theatre staff, facilities managers and other appropriate people.


Features and benefits:

  • Extensive range of solutions.
  • Compactness.
  • Efficiency up to >96.6%.
  • High power availability.
  • Smart battery management.
  • Maximum reliability.
  • Flexibility of use.
  • Robust and reliable.
  • Galvanic isolation.
  • High overload capacity.
  • Hot System Expansion (HSE).
  • Multiple controls.
  • Highly flexible.
  • Utmost availability.
  • Ultimate scalability.
-
-
Color
Grey, Black
-
-
Finish
Powder-coated
-
-
Material
Metal
-
-
Shape
Rectangle
-
-
Length
Bespoke
-
-
Width
Bespoke
-
-
Height
Bespoke
-
-

Specification

Classification data
Standards
To BS EN IEC 62040-1 and BS EN 62040-3.
-
-
Test requirements
Submit type test certificates.
-
-
Mode of operation
Online.
-
-
Configuration
Parallel with bypass.
-
-
Efficiency
-
-
-
Overall (minimum)
96.6%.
-
-
Eco mode (minimum)
99%.
-
-
Load compatibility
Suitable for use with loads operating at any power factor (leading or lagging) up to 0.9.
-
-
Input
-
-
-
Nominal voltage
Single-phase 230 V a.c., Three-phase 400 V a.c.
-
-
Voltage tolerance
±20% at full load.
-
-
Frequency
50 Hz., 60 Hz.
-
-
Power factor
>0.99 at full load.
-
-
Input current distortion (THDi)
≤3%.
-
-
Inrush current
Manufacturer's standard.
-
-
Inverter output
-
-
-
Rated output apparent power
20 kV·A.
-
-
Nominal voltage
Single-phase 220 V a.c., Single-phase 230 V a.c., Single-phase 240 V a.c.
-
-
Voltage tolerance
±1%.
-
-
Voltage waveform
Sinusoidal in both normal and stored energy mode of operation.
-
-
Voltage distortion
<1% with resistive linear load / ≤1.5% with non-linear load.
-
-
Nominal frequency
50 Hz., 60 Hz.
-
-
Frequency tolerance
±0.01%.
-
-
Overload capability
110% infinite, 125% for 60 min, 150% for 10 min.
-
-
Output power factor (minimum)
1.
-
-
Crest factor
Manufacturer's standard.
-
-
Galvanic separation between input and output
Not required., Required.
-
-
Integral bypass operation
-
-
-
Automatic transfer of the load to the bypass source under the following conditions
Fault condition.
-
-
Re-transfer of the load from the bypass source
Automatic unless under manual control or fault conditions are present.
-
-
Maintenance bypass
Not required.
-
-
Batteries
-
-
-
Location
Separate battery enclosures.
-
-
Type
VRLA AGM., GEL., NiCd., Li-ion., SuperCaps.
-
-
Voltage
12 V.
-
-
Controls, indicators and alarms
-
-
-
LCD display
UPS status led bar - Graphic touch screen display.
-
-
Audible alarms
-
-
-
Type
Integral alarm within UPS enclosure.
-
-
Activation and reset
Activated by any fault condition. Continuous output until fault cleared or alarm silenced. Silencing of the alarm must not clear LED status indication.
-
-
Communications and signalling
USB., RS 232 port.
-
-
Enclosure
-
-
-
Ingress protection (minimum)
IP20.
-
-
Material and construction
-
-
-
Type
Welded carbon steel. Assemble to prevent distortion when the complete enclosure is lifted or transported.
-
-
Finish
Epoxy powder-coated.
-
-
Colour
RAL 7016 Anthracite grey.
-
-
Cable entry with removable gland plates
For top entry cables., For bottom entry cables., For front entry cables.
-
-
Ventilation arrangement
-
-
-
Type
Actively controlled fan ventilation.
-
-
Fan failure alarms
Required.
-
-
Noise emission
-
-
-
Sound pressure level in normal mode (maximum)
<40 dBA at 1 m.
-
-

Sustainability data

Material
Metal
-
-