NBS Source
I'm a manufacturer

Compare variants

CX Gas Floor Standing Cabinet Heater
CX Gas Floor Standing Cabinet Heater
CX Gas Floor Standing Cabinet Heater

Verified 17 days ago

Powrmatic Ltd

Verified 17 days ago

Powrmatic Ltd

Verified 17 days ago

Powrmatic Ltd
Summary
Gas cabinet heater with direct airflow or ducted output.
-
-
Application

Suitable for free-blowing and ducted heating applications.

-
-
Description

Ultra low NOx cabinet heater offering high performance and efficiency for heating applications.


Features and benefits:

  • Ten outputs ranging from 30 kW through to 300 kW.
  • Adjustable heat distribution.
  • Availability of horizontal types for applications where space and air direction is specific.
  • Burner technology and access cover.
  • All CX are supplied with a fitted and tested burner.
  • ErP 2021 reduced NOx emissions.
  • CX is available as upright (UF or UD) versions.
  • CX is available as horizontal (HF or HD) versions.
  • CX is available as an external (EA) version.
  • CX heaters are type tested and CE approved.
-
-
Color
Grey
-
-
Finish
Painted
-
-
Material
Stainless steel
-
-
Shape
Rectangle
-
-
Length
732 mm, 927 mm, 1200 mm, 1399 mm, 1599 mm, 1767 mm, 1895 mm, 2151 mm, 2265 mm
-
-
Width
668 mm, 732 mm, 744 mm, 904 mm, 927 mm, 1104 mm, 1200 mm, 1399 mm, 1599 mm
-
-
Height
819 mm, 894 mm, 1054 mm, 1254 mm, 1767 mm, 1895 mm, 2149 mm, 2265 mm
-
-
Warranty description
Two year
-
-
SKU Code
CX UD 30, CX UD 45, CX UD 60, CX UD 90, CX UD 120, CX UD 150, CX UD 175, CX UD 200, CX UD 250, CX UD 300, CX UF 30, CX UF 45, CX UF 60, CX UF 90, CX UF 120, CX UF 150, CX UF 175, CX UF 200, CX UF 250, CX UF 300, CX HF 30, CX HF 45, CX HF 60, CX HF 90, CX HF 120, CX HF 150, CX HF 175, CX HF 200, CX HF 250, CX HF 300, CX HD 30, CX HD 45, CX HD 60, CX HD 90, CX HD 120, CX HD 150, CX HD 175, CX HD 200, CX HD 250, CX HD 300, CX EA 30, CX EA 45, CX EA 60, CX EA 90, CX EA 120, CX EA 150, CX EA 175, CX EA 200, CX EA 250, CX EA 300
-
-

Specification

Classification data
Output
High fire: 119.2 kW (maximum). Low fire: 39.8 kW (minimum).
-
-
Air volume
1.9 m³/s.
-
-
Arrangement
Horizontal., Upright.
-
-
Position
External., Internal.
-
-
Outlets
Free-blowing., Ducted.
-
-
Fuel
Natural gas.
-
-
Burner
Inverterjet burner.
-
-
Controls
Heating controller.
-
-
Flues and chimneys
Supplied with 90° flue tee.
-
-
Accessories
Side and rear inlet spigots., Filters., Dampers.
-
-

Additional properties

Input
High fire: 128.2 kW (maximum).
Low fire: 40.5 kW (minimum).
-
-
Model
CX UF - Upright, freeblowing., CX UD - Upright, ducted., CX HF - Horizontal, freeblowing., CX HD - Horizontal, ducted., CX EA - External.
-
-
Diameter
Flue: Ø150 mm.
Combustion air spigot: Ø130 mm.
-
-
Net weight
341 kg.
-
-
HeatingEfficiency
80.2%.
-
-
Connection
¾" BSP.
-
-
InputPressure
17.5 mbar.
-
-
Noise
69 dB(A).
-
-

Sustainability data

Contains Red List materials
No
-
-
Country of material origin
United Kingdom
-
-
Country of product manufacture
United Kingdom
-
-