Delta 800 Series Bespoke Packaged Pump Station (Foul Water) - Packaged Pump Station
Delta 800 Series Bespoke Packaged Pump Station (Foul Water) - Packaged Pump Station
Delta 800 Series Bespoke Packaged Pump Station (Foul Water) - Packaged Pump Station

Verified 5 months ago

Delta Membrane Systems Ltd

Verified 5 months ago

Delta Membrane Systems Ltd

Verified 5 months ago

Delta Membrane Systems Ltd
Summary
The Delta Bespoke 800 Series of Packaged Pumping Station are available in depths from 1250 mm to 2000 mm and with varying pumping capabilities from the Delta Single V3 Foul to the Delta Dual V3 Foul.
-
-
Application

Designed specifically for below ground applications to collect foul water/ grey water.


How to video guide - Installation of a Delta 800 Series Pumping Station - Delta Membranes


The Delta Bespoke 800 Series – Single/ Dual V3 Foul 800 Series is not suitable for collecting ground water from a cavity drained membrane system.

-
-
Description

The robust and reliable Delta Bespoke 800 Series Packaged Pumping Station has been specifically designed to collect foul and/ or grey water from basements, below ground structures and ground floor extensions or where foul water cannot be drained by gravity. The Delta Bespoke 800 Series – Single/ Dual V3 Foul can accept waste from an extension, outbuilding, basement or similar, where the structure also has another method of removing foul water.


The system includes a polyethylene chamber, Single or Dual Delta Foul V3 sump pumps, pump pedestal with guide rail, 110 mm inlet, 110 mm cable duct, 110 mm vent and 2” discharge.


It is specifically designed for below ground applications where hydrostatic water pressure may be present. However, it is recommend that the Delta Bespoke 800 Series – Single/ Dual V3 Foul is surrounded with concrete to prevent movement. A manhole cover is not supplied as these are generally site specific and installed in the final finish.


Features and benefits:

  • Large chamber, manufactured from superior polyethylene enabling the – Delta V3 Foul to withstand hydrostatic forces encountered in applications with high water tables.
  • Quick and simple installation.
  • Supplied with Single or Dual Delta Foul V3 Pump.
  • Flow rate of Delta Foul V3 Pump up to 6.3 L/s.
  • For kitchen applications it is recommended that a grease trap is fitted prior to the pump station installation.
  • Please contact manufacturer if a foul water packaged pumping station to serve the whole property is required.
  • Not suitable for collecting ground water from a cavity drained membrane system.
  • UKCA and CE marked.
-
-
Digital objects
-
-
Color
White
-
-
Material
High density polyethylene (HDPE)
-
-
Shape
Other
-
-
Width
800 mm
-
-
Height
1250 mm, 1500 mm, 1750 mm, 2000 mm
-
-
SKU Code
DMS-E013 SFV3.800.1250, DMS-E014 SFV3.800.1500, DMS-E015 SFV3.800.1750, DMS-E016 SFV3.800.2000, DMS-E017 DFV3.800.1250, DMS-E018 DFV3.800.1500, DMS-E019 DFV3.800.1750, DMS-E020 DFV3.800.2000
-
-

Specification

Standards
To BS EN 12050-3:2015.
-
-
Collection tank
-
-
-
Material
Polyethylene.
-
-
Type
Vertical.
-
-
Configuration
Wet well.
-
-
Capacity (minimum)
200 L.
-
-
Pumps
-
-
-
Configuration
Twin pumps.
-
-
Impeller
Vortex.
-
-
Pump characteristic
6.3 L/s at 12 m head.
-
-
Non-return valve
Required.
-
-
Connections
-
-
-
Inlet diameter
DN 110.
-
-
Vent pipes
-
-
-
Material
PVC Class E.
-
-
Diameter
DN 110.
-
-
Control
Control panel.
-
-

Additional properties

Dimensions
Ø800 x 1250 mm.
-
-

Sustainability data

Contains Red List materials
No
-
-
Country of product manufacture
United Kingdom
-
-
Material
High density polyethylene (HDPE)
-
-
Recyclability
Yes
-
-
Recycled content
0 %
-
-