UG - gaSteam - Gas-Fired Steam Humidifier Range
UG - gaSteam - Gas-Fired Steam Humidifier Range
UG - gaSteam - Gas-Fired Steam Humidifier Range

Verified 5 months ago

CAREL

Verified 5 months ago

CAREL

Verified 5 months ago

CAREL
Summary
Range of humidifiers running on natural gas, a clean, sustainable and economical source of energy. It produces steam from both mains water and demineralized water.
-
-
Application

Available in the indoor and outdoor versions. The outdoor version, designed to eliminate the risk of having a gas source inside the building and allow it to be used when no equipment room is available, produces steam even in the most critical situations and without the need for outdoor cabinets or compartments.


The gaSteam outdoor version has been designed to withstand both high temperatures and especially climates or environments where the temperatures are very low (-40 to 45°C).

-
-
Description

Range of humidifiers running on natural gas, a clean, sustainable and economical source of energy. It produces steam from both drinkable mains water and demineralized water.

Available in the indoor and outdoor versions. The outdoor version, designed to eliminate the risk of having a gas source inside the building and allow it to be used when no equipment room is available, produces steam even in the most critical situations and without the need for outdoor cabinets or compartments.


Features and benefits:

  • Exceptional relative humidity control performance (±2%).
  • Wide range of models with steam production from 45 to 450 kg/h.
  • Outdoor version for critical temperatures and when no equipment room or compartment is available.
  • The gaSteam outdoor version has been designed to withstand both high temperatures and especially climates or environments where the temperatures are very low (-40 to 45°C).
  • Minimum installation space.
  • Built-in remote supervision available.
  • Hygiene: If there is no demand for humidity for more than three consecutive days, the water is automatically drained to ensure maximum hygiene.
  • Fuel supply: Can be supplied with natural gas or LPG. The gas is selected directly in the pre-mix burner calibration software.


Control features:

  • Configuration wizard.
  • Advanced control.
  • Modulating limit probe.
  • Backup and rotation.
  • Active room and duct probes: 0–1 V, 0–10 V; 2–10 V; 0–20 mA; 4–20 mA.
  • Modulating limit probe with 0–1 V; 0–10 V; 2–10 V; 0–20 mA; 4–20 mA signals.
  • Signals: 0–1 V, 0–10 V; 2–10 V; 0–20 mA; 4–20 mA and ON/OFF.
  • Wireless probes.
  • Alarm relay for lights/ audible signals.
  • Built-in USB port.


Features common to both models:

  • Raised base to avoid damage due to water stagnation.
  • Smallest possible footprint.
  • The boiler can be opened and inspected both from the top, with complete and rapid removal of the cover, and from the bottom for cleaning and removing any scale.
  • Possibility to access the unit from all sides.
  • Flame control: control system connected to the electrical panel that detects the flame and automatically reignites.
  • Temperature control system: system for controlling and managing the unit parameters, protecting the outdoor humidifier.
  • The exclusive design of the heat exchanger ensures high efficiency (94–96%) and easy maintenance.
  • Pre-heating: this function keeps the water in the boiler at a temperature that can be set by the user for an immediate response.
  • 4.3” touchscreen display.


Certifications:

CE, ETL (UL998), TÜV and AGA

In addition for the outdoor version: ETL in accordance with IAS standard (No. 12-94) for outdoor installations.

-
-
Product certifications
-
-
Digital objects
-
-
Color
White
-
-
Finish
Galvanized
-
-
Material
Metal
-
-
Shape
Rectangle
-
-
Length
1443 mm, 1560 mm, 1620 mm
-
-
Width
656 mm, 800 mm, 993 mm, 1107 mm, 1668 mm
-
-
Height
1603 mm
-
-
Warranty description
Two year
-
-
SKU Code
UG045, UG090, UG150, UG180, UG300, UG450
-
-

Specification

Classification data
Electrical supply type
Single phase, 230 V a.c., 50 Hz (D005)., Single phase, 115 V a.c., 60 Hz (D105).
-
-
Steam source
Gas fired.
-
-
Material
Stainless steel.
-
-
Access doors for maintenance
Manufacturer's standard.
-
-
Accessories
None., DP/*R0 lance for duct (standard)., DP/*RU lance for duct (high capacity)., DP/*RH lance for duct (high efficiency)., Hoses., Probe - DPW* wall sensor., Probe - DPP* sensor for industrial environments., Probe - DPD* duct sensor., Probe - ASET* temperature sensor for steam baths.
-
-

Additional properties

Model
Outdoor; 1–45°C (Y)., Outdoor, modulation; -40–45°C (X).
-
-
Dimensions
1560 x 800 x 1603 mm.
-
-
Weight
255 kg.
-
-
Network type
Modbus®., BacNET., Modbus Ethernet., BacNET Ethernet.
-
-
Steam
Rated production: 90 kg/h.
Steam production modulation: 25–100%.
-
-
Power consumption
250 W at rated voltage.
-
-
Connections
Steam: 1 x 80 mm diameter.
Gas: 1 x 1"G.
Water fill: 1 x ¾"G male.
Water drain: 1 x 50 mm diameter.
Exhaust flue: 1 x 80 mm diameter.
Flue connection: 1 x 80 mm diameter.
-
-
Pressure
Steam outlet pressure limits: 0–2000 Pa (0–0.3 psi).
-
-
Conditions
Operating: 1 to 40°C, 10–60% relative humidity.
Storage: -10 to 70°C, 5–95% relative humidity.
-
-
Water
Fill:
· Temperature limits, indoor operating conditions: 1 to 40°C; outdoor operating conditions: -40 to 45°C.
· Water pressure limits: 0.1 to 0.8 MPa (1 to 8 bar).
· Instant flow rate: 18 L/m.
· Total hardness: 4 to 40°fH.
· Conductivity limits: 1500 μS/cm.
Drain:
· Temperature: <100°C.
· Instant flow rate: 32 L/m.
-
-
Fuel
Natural gas., LPG.
-
-
Heat
Gross input: 65 kW.
Net output: 62.5 kW.
-
-
Ingress protection
IAS 12–94.
-
-
Controller
Continuous modulation: 25–100%.
Built-in control: rH or temperature (probes not included).
Proportional to external signal: Yes.
Limit probe: Yes.
Remote ON/OFF: Yes.
Alarm relay: Yes.
Signal type (probe or external controller): 0–10 V; 0–1 V; 2–10 V; 0–20 mA; 4–20 mA.
Supervisor (via RS485 and Ethernet): Yes.
-
-
Gas
Flue gas flow-rate (natural gas G20): 0.0303 kg/s.
Flue gas temperature (natural gas G20): 170°C.
NOx emissions class: 5.
-
-
Third-party certification
CE; ETL (UL998); TÜV and AGA.
ETL in accordance with IAS standard (No. 12-94).
-
-