CS Rain Defence Louvres RSH-5700
CS Rain Defence Louvres RSH-5700

Verified 4 months ago

Construction Specialties (UK) Ltd

Standard frame

Verified 4 months ago

Construction Specialties (UK) Ltd

Glazing frame

Summary
High performance louvres with horizontal blades and visible mullions, offering great protection against wind-driven rain penetration and good airflow. Classified as Class A 3 up to 3.0 m/s.
High performance louvres with horizontal blades and visible mullions, offering great protection against wind-driven rain penetration and good airflow. Classified as Class A 3 up to 3.0 m/s.
Digital objects
Color
Silver, Other
Silver, Other
Finish
Mill, Anodized, Powder-coated
Mill, Anodized, Powder-coated
Material
Aluminium
Aluminium
Length
129 mm
129 mm
Width
Bespoke
Bespoke
Height
Bespoke
Bespoke

Specification

Material
All components to be one-piece members extruded from aluminium alloy 6063-T6 (nominal thickness of heads, cills, jambs and mullions to be minimum 1.91 mm; blades to be minimum 1.52 mm).
All components to be one-piece members extruded from aluminium alloy 6063-T6 (nominal thickness of heads, cills, jambs and mullions to be minimum 1.91 mm; blades to be minimum 1.52 mm).
Finish
Milled., Anodized, clear., Anodized, colour., Polyester powder-coated finish, matt, colour., Polyester powder-coated finish, gloss, colour.
Milled., Anodized, clear., Anodized, colour., Polyester powder-coated finish, matt, colour., Polyester powder-coated finish, gloss, colour.
Colour
As Finish.
As Finish.
Construction
Supplied as modules, mechanically assembled in the factory using stainless steel fasteners. Multiple module installations to include interlocking visible mullions with drainage channels.
Supplied as modules, mechanically assembled in the factory using stainless steel fasteners, and complete with a 25 mm glazing frame, suitable for fitting into glazing sockets or use in Structural Silicone Glazing (SSG) system.
Weather performance
-
-
Water penetration class (minimum)
To BS EN 13030, class A up to 3.0 m/s.
To BS EN 13030, class A up to 3.0 m/s.
Discharge loss coefficient (minimum)
To BS EN 13030, class 3: Airflow coefficient Ce (entry): 0.289; Cd (discharge): 0.284.
To BS EN 13030, class 3: Airflow coefficient Ce (entry): 0.289; Cd (discharge): 0.284.
Louvre configuration
-
-
Number of banks
One.
One.
Blade orientation
Horizontal.
Horizontal.
Blade pitch
51 mm.
51 mm.
Blade angle
Complex extruded blade profile.
Complex extruded blade profile.
Accessories
None., Bird/ vermin guard, galvanized steel welded mesh., Bird/ vermin guard, expanded aluminium welded mesh., Insect mesh, PVC-coated fibreglass., Louvred door(s)., Dampers, high-performance PVC-U, volume control., Dampers, aluminium, volume control., Snap-on cover plate to close-off louvre frame.
None., Bird/ vermin guard, galvanized steel welded mesh., Bird/ vermin guard, expanded aluminium welded mesh., Insect mesh, PVC-coated fibreglass., Louvred door(s)., Dampers, high-performance PVC-U, volume control., Dampers, aluminium, volume control., Snap-on cover plate to close-off louvre frame.

Additional properties

Cill pan
Louvres to be supplied with a full depth cill pan with welded side panels, formed from 2 mm-thick aluminium.
-
Blanking panels
Not required., Single-skin aluminium panels, to match louvre., Single-skin aluminium panels, mill finish., Single-skin aluminium panels, other colour/ finish., Insulated panels incorporating A1-classified non-combustible stone wool core., Insulated panels, extruded polystyrene core.
Not required., Single-skin aluminium panels, to match louvre., Single-skin aluminium panels, mill finish., Single-skin aluminium panels, other colour/ finish., Insulated panels incorporating A1-classified non-combustible stone wool core., Insulated panels, extruded polystyrene core.
Burglar resistance
Required (To EN 1627–1630, RC2)., Not required.
Required (To EN 1627–1630, RC2)., Not required.
Blast resistance
Required., Not required.
Required., Not required.