NBS Source
I'm a manufacturer

Compare variants

LUNOS Nexxt E - Heat Recovery Ventilation - Decentralised Ventilation System
LUNOS Nexxt E - Heat Recovery Ventilation - Decentralised Ventilation System

Verified 4 months ago

PARTEL

Nexxt E Surface Mounted

Verified 4 months ago

PARTEL

Nexxt E Flush Mounted

Summary
A decentralised ventilation unit with heat recovery, due to its high volume flow it is ideally suited for use in schools, offices, hotels, doctors' surgeries, but also for flats and houses.
A decentralised ventilation unit with heat recovery, due to its high volume flow it is ideally suited for use in schools, offices, hotels, doctors' surgeries, but also for flats and houses.
Color
White
White
Shape
Rectangle
Rectangle
Length
170 mm, 66 mm, 72 mm
170 mm, 66 mm, 72 mm
Width
480 mm, 510 mm, 235 mm
480 mm, 510 mm, 235 mm
Height
480 mm, 510 mm, 205 mm
480 mm, 510 mm, 205 mm

Specification

Standards
-
-
Performance testing
To BS EN 13141-8.
To BS EN 13141-8.
Duty
4–31 L/s.
4–31 L/s.
Mounting
Wall, surface.
Wall, flush.
Controls
Integral humidity sensor.
Integral humidity sensor.

Additional properties

Free area
Equivalent free area (EN 13141-1): 4000 mm2.
Equivalent free area (EN 13141-1): 4000 mm2.
SoundPressure
At 1 m distance: 12–49 dB(A); At 3 m distance: 2–39 dB(A).
At 1 m distance: 12–49 dB(A); At 3 m distance: 2–39 dB(A).
Ingress protection (IP) rating
IP22.
IP22.
Voltage
200–240 V (50/60 Hz)., 115 V (60 Hz).
200–240 V (50/60 Hz)., 115 V (60 Hz).
Minimum wall thickness
110 mm.
280 mm.
Integral accessories
Wall-tubes for the series 160, two-way outer hood, Nexxt inner screen with operating element, Nexxt installation housing and Nexxt surface-mounting set.
Wall-tubes for the series 160, two-way outer hood, Nexxt inner screen with operating element, Nexxt installation housing.
Energy rating
Energy efficiency class A.
Energy efficiency class A.
Dimensions
Core drilling: 162 mm; Minimum installation length: 110 mm.
Core drilling: 162 mm; Minimum installation length: 280 mm.
Heat
Degree of heat supply: 83% (maximum). Heat supply level to EN 13141-8: 73%.
Degree of heat supply: 83% (maximum). Heat supply level to EN 13141-8: 73%.

Sustainability data

Contains Red List materials
No
No