Summary
Air-to-water monobloc system.
-
-
Application

Suitable for external applications where indoor space is limited.

-
-
Description

An outdoor single unit low temperature air-to-water heat pump with the option of heating only or reversible systems.


Features and benefits:

  • Monobloc all-in-one concept including hydraulic parts.
  • Optional W-LAN cartridge.
  • Possible to combine with domestic hot water.
  • Controllable environment from any location via smartphone or tablet through the Onecta app.


For full technical information, refer to manufacturer's literature.


EBLA(09/11/14/16)D3W1 and EBLA(09/11/14/16)D3V3:

  • Reversible air to water monobloc system.
  • Energy efficient heating and cooling system based on air to water heat pump technology.
  • Built-in electric back-up heater as additional heating during extremely cold outdoor temperature.


EDLA(09/11/14/16)D3W1 and EDLA(09/11/14/16)D3V3:

  • Heating only air to water monobloc system.
  • Energy efficient heating only system based on air to water heat pump technology.
  • Built-in electric back-up heater as additional heating during extremely cold outdoor temperature.
-
-
Color
Silver, Black
-
-
Finish
Coated
-
-
Material
Steel, Stainless steel
-
-
Shape
Rectangle
-
-
Length
460 mm
-
-
Width
1380 mm
-
-
Height
870 mm
-
-
Warranty description
Five year
-
-

Specification

Standards
-
-
-
Test requirements
To BS EN 14511.
-
-
Heat pump type
Monobloc.
-
-
Mode
Heating and cooling.
-
-
Coefficient of performance (minimum)
4.91 (condition 1); 3.71 (condition 2).
-
-
Output
-
-
-
Heating
9.37 kW (condition 1); 9.00 kW (condition 2).
-
-
Cooling
9.35 kW (cooling 3); 9.10 kW (cooling 4).
-
-
Fan
-
-
-
Type
Propeller.
-
-
Fan drive
Direct.
-
-
Configuration
Horizontal.
-
-
Electrical supply type
Three phase.
-
-
Compressor
-
-
-
Type
Swing.
-
-
Sealing
Hermetically sealed.
-
-
Drive
Inverter driven.
-
-
Accessories
Back up heater kit., Not required.
-
-
Refrigerant
R32.
-
-

Additional properties

Dimensions
870 x 1380 x 460 mm.
-
-
Unit weight
147 kg.
-
-
Sound
To EN14825, 62.0 dB(A).
-
-
Safety devices
High pressure switch, low pressure switch, fan driver overload protector, fuse, and compressor motor thermal protector.
-
-
PipeConnection
G 1" (male).
-
-
Air flow
2880 m³/h.
-
-
HeatingWaterFlowRate
26.9 L/min (condition 1); 25.8 L/min (condition 2).
-
-
CoolingWaterFlowRate
26.8 L/min (cooling 3); 26.1 L/min (cooling 4).
-
-
Motor
400 rpm (heating); 500 rpm (cooling).
-
-
Material
Polyester painted galvanized steel plate.
-
-
Casing colour
Silver.
-
-

Sustainability data

Country of material origin
Europe
-
-
Country of product manufacture
Europe
-
-