NBS Source
I'm a manufacturer

TBA Firefly Penowrap®

Verified by manufacturer over a year ago

TBA Firefly

Thin, lightweight, flexible wrap, can be used by Fire Engineers to design support systems which will withstand attack from fire for a period of 2 hours.

Jump to:
+61754114209 Website

Application

TBA Firefly™ Penowrap® is used in conjunction with other TBA Firefly™ products to maintain the FRL of various walls, floors and ceilings where they are penetrated by either structural or service penetrations.  


Tested systems include: 

  • Steel universal beams.
  • Timber beams.  
  • C and Z purlins. 
  • Various service penetrations. 
  • All sizes and bundles of power and communication cables used in Australia (with or without Steel Cable Trays).
  • Full range of VASS, EAE, ABB and IPD Electrical Busducts with either copper or aluminium conductor.  


Suitable for support systems which carry:

  • Ductwork.
  • Large sprinkler pipes.
  • Fire Rated Boxouts & Enclosures.
  • Electrical Busways.
  • Electrical Cable Trays etc.

Description

TBA Firefly™ Penowrap® is a thin, lightweight, flexible wrap which has extremely high Fire Resistance capabilities when used as a component of TBA Firefly™ systems, when tested in accordance with AS1530.4-2014 and assessed in accordance with AS4072.1-2005.


  • The steel support systems protected with TBA Firefly™ Penowrap® have been shown to meet the Performance Requirements of the NCC.
  • Withstood the loads applied and maintained these loads without collapse for a period of 2 hours when tested in accordance with AS1530.4-2014.

General information

Warranty description

25 year

Uniclass

Pr_25_80_80_14 Coated woven glass fibre cloth flexible cavity barriersPrimary

NATSPEC National Classification System

0182 Fire-Stopping

SpecPack

07810 Fireproofing

SpeedSpec

07810 Fireproofing

Specification data - Coated woven glass fibre cloth flexible cavity barriers

Thickness

12 mm.

Fire performance

-

Fire resistance level

-

Standard

To AS 1530.4 and AS 4072.1.

Value

-/120/120.

Certification

Warringtonfire.

Guidance for specification option:

  • FAS190234 RIR.
  • FAS190235 RIR.
  • FAS190236 RIR.

CSIRO.

Guidance for specification option:

  • FCO-3228 SFA.

Execution

-

Manufacturer guidance

TBA FIREFLY™ PENOWRAP® is to be installed in strict compliance accordance with the concise construction details contained within the reports.