Long span fire curtain system.
Suitable for theatres, warehouses, hospitals, office buildings, shopping centres, atriums, openings in external walls and fire compartment walls, construction of proscenium walls and servery openings in smoke-proof walls for healthcare and residential care buildings.
Fibershield V is a long span fire curtain system. It is the only system available full scale fire tested with sprinklers to provide a fire resistance of -/120/120. Some of its features include:
Shape | Rectangle. |
WarrantyDescriptionExtended warranty available with back to back maintenance agreement. | One year. Standard warranty. |
Uniclass | Pr_25_80_79_94 Vertical active fire curtain barriers Primary |
SpecPack | 08330 Roller Shutter Doors 10240 Grilles and Screens |
NATSPEC National Classification System | 0454 Overhead Doors 1002 Fire Services Design and Install |
SpeedSpec | 08330 Roller Shutter Doors |
Performance | - |
Fire resistance level | - |
Standard | To AS 1530.4. |
Value | -/120/- (minimum).-/120/120 (when used with sprinklers). |
Smoke leakage | - |
Standard | To EN 12101-1. |
ValueRefers to fabric permeability only. | ≤ 25 m³/h. |
Fire hazard properties | - |
Standard | To AS/NZS 1530.3 and AS 3837. |
Group numberTested in accordance with AS 3837. | 1. |
Spread of flame indexTested in accordance with AS 1530.3. | 0. |
Smoke developed index | 1. |
Durability | 10 000 open-close cycles. |
Closing timeRefers to nominal value. | 150 mm/s (for sizes up to 20 m W x 6 m H).90 mm/s (for sizes up to 30 m W x 10 m H). |
Time delay for deploymentUpon receipt of alarm. | - |
Time delay for rewindUpon reset of the Fire Indicator Panel. This is applicable to the building fire alarm system rather than the curtain system. | - |
Battery back-upCan be provided as an optional extra. | - |
Curtain | - |
Material | Woven stainless steel and fiberglass matrix. |
Size and shape (maximum)Available in sizes up to 30 m W x 10 m H. Contact local manufacturer for specific dimension needs. | - |
Head box | - |
SizeWidth varies depending on specified curtain size. For widths greater than 20 m, contact local manufacturer. | 200 mm H x 190 mm D (for curtain heights up to 3.5 m).250 mm H x 190 mm D (for curtain heights up to 6 m).290 mm H x 235 mm D (for curtain heights up to 9 m). |
Side guides | - |
SizeFor widths greater than 20 m, contact local manufacturer. | 105 mm W x 74 mm D (system size up to 12 m W x 6 m H).160 mm W x 100 mm D (system size up to 20 m W x 10 m H). |
Controls | Control box.
|
Integral accessories | Alarm signal.Should be in the form of a normally closed dry contact. A localised smoke or heat detector may also be used. |
Fire barrierRefers to Fire Shutter performance data. | To AS 1905.2. |
Box weightRefers to system weight. For heights over 6 m, contact local manufacturer. | 25 kg/m of system width (for curtain heights up to 3 m). 30 kg/m of system width (for curtain heights up to 4 m). 40 kg/m of system width (for curtain heights up to 6 m). |
MaximumWorkingPressureRefers to maximum pressure resistance. For curtains greater than 100 m², contact local manufacturer. | 100 Pa (fully closed curtain up to 50 m²). 50 Pa (fully closed curtain up to 100 m²). |
Optional features | Battery back-up. Rewind switches. Rewind switches are optionally available for direct connection to the control box. Curtain retraction will be based on a set timer. Curtain applied signage. Self-levelling bottom bar covers. |
Installation | To be installed by Smoke Control approved installer network. |
Country of product manufacture | Germany |