Verified by manufacturer over a year ago
Long span fire curtain system.
Suitable for theatres, warehouses, hospitals, office buildings, shopping centres, atriums, openings in external walls and fire compartment walls, construction of proscenium walls and servery openings in smoke-proof walls for healthcare and residential care buildings.
Fibershield V is a long span fire curtain system. It is the only system available full scale fire tested with sprinklers to provide a fire resistance of -/120/120. Some of its features include:
Color | Silver |
Shape | Rectangle |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Warranty description | One year Guidance for specification option: Standard warranty. Manufacturer guidanceExtended warranty available with back to back maintenance agreement. |
Uniclass | |
SpecPack | 08330 Roller Shutter Doors 10240 Grilles and Screens |
NATSPEC National Classification System | 0454 Overhead Doors 1002 Fire Services Design and Install |
SpeedSpec | 08330 Roller Shutter Doors |
Performance | |
Fire resistance level | |
Standard | To AS 1530.4. |
Value | -/120/- (minimum).-/120/120 (when used with sprinklers). |
Smoke leakage | |
Standard | To EN 12101-1. |
Value | ≤ 25 m³/h.Manufacturer guidanceRefers to fabric permeability only. |
Fire hazard properties | |
Standard | To AS/NZS 1530.3 and AS 3837. |
Group number | 1.Manufacturer guidanceTested in accordance with AS 3837. |
Spread of flame index | 0.Manufacturer guidanceTested in accordance with AS 1530.3. |
Smoke developed index | 1. |
Durability | 10 000 open-close cycles. |
Closing time | 150 mm/s (for sizes up to 20 m W x 6 m H).90 mm/s (for sizes up to 30 m W x 10 m H).Manufacturer guidanceRefers to nominal value. |
Time delay for deployment | Manufacturer guidanceUpon receipt of alarm. |
Time delay for rewind | Manufacturer guidanceUpon reset of the Fire Indicator Panel. This is applicable to the building fire alarm system rather than the curtain system. |
Battery back-up | Manufacturer guidanceCan be provided as an optional extra. |
Curtain | |
Material | Woven stainless steel and fiberglass matrix. |
Size and shape (maximum) | Manufacturer guidanceAvailable in sizes up to 30 m W x 10 m H. Contact local manufacturer for specific dimension needs. |
Head box | |
Size | 200 mm H x 190 mm D (for curtain heights up to 3.5 m).250 mm H x 190 mm D (for curtain heights up to 6 m).290 mm H x 235 mm D (for curtain heights up to 9 m).Manufacturer guidanceWidth varies depending on specified curtain size. For widths greater than 20 m, contact local manufacturer. |
Side guides | |
Size | 105 mm W x 74 mm D (system size up to 12 m W x 6 m H).160 mm W x 100 mm D (system size up to 20 m W x 10 m H).Manufacturer guidanceFor widths greater than 20 m, contact local manufacturer. |
Controls | Control box.Guidance for specification option:
|
Integral accessories | Alarm signal.Guidance for specification option: Should be in the form of a normally closed dry contact. A localised smoke or heat detector may also be used. |
Fire barrier | To AS 1905.2. Manufacturer guidanceRefers to Fire Shutter performance data. |
Box weight | 25 kg/m of system width (for curtain heights up to 3 m). 30 kg/m of system width (for curtain heights up to 4 m). 40 kg/m of system width (for curtain heights up to 6 m). Manufacturer guidanceRefers to system weight. For heights over 6 m, contact local manufacturer. |
MaximumWorkingPressure | 100 Pa (fully closed curtain up to 50 m²). 50 Pa (fully closed curtain up to 100 m²). Manufacturer guidanceRefers to maximum pressure resistance. For curtains greater than 100 m², contact local manufacturer. |
Optional features | Battery back-up. Rewind switches. Guidance for specification option: Rewind switches are optionally available for direct connection to the control box. Curtain retraction will be based on a set timer. Curtain applied signage. Self-levelling bottom bar covers. |
Installation | To be installed by Smoke Control approved installer network. |
Country of product manufacture | Germany |