Verifierad av tillverkaren för 3 månader sedan
DoP
Certifikattyp
EPD
Certifikattyp
High performance rigid phenolic thermal pipe insulation used primarily for the insulation of chilled, cold, hot and heating pipe work.
Primarily for use in the lagging of chilled, cold, hot and heating pipe work.
Supaphen is a high performance rigid phenolic thermal pipe insulation used primarily for the lagging of chilled, cold, hot and heating pipe work. It complies with the requirements of product standard BS EN 14314 Thermal insulation products for building equipment and industrial installations – factory made phenolic foam (PF) products.
Features and benefits:
Färg | Green |
ytbehandling | Foil |
Material | Phenolic foam |
Längd | Bespoke |
Bredd | Bespoke |
Höjd | Bespoke |
Garantibeskrivning | Ten year |
Uniclass | |
CAWS | S90/570 Insulation to pipelines S90/570 Insulation to pipework |
Klassificeringsdata | |
Standard | To BS EN 14314. |
Form | Pipe section. |
Thermal conductivity | To EN 12667, 0.025 W/m·K at 10°C. |
Finish | Aluminium. |
Fire performance | To EN 13501-1, BL–s1,d0. Vägledning för specifikationsalternativ: Achieved on 25 mm and 50 mm thick foiled pipe section. |
Environmental rating | Environmentally safe - CFC- and HCFC-free; GWP lass than 5; Zero Ozone Depletion Potential (ODP). |
Insulation thickness (minimum) | To BS 5422. |
Vapour barrier | |
Material | Aluminium foil. Vägledning för specifikationsalternativ: Standard. Fire-rated aluminium foil vapour barrier applied to the Supaphen pipe sections. Proclad, silver. Vägledning för specifikationsalternativ: Optional factory-applied facing. Proclad, embossed. Vägledning för specifikationsalternativ: Optional factory-applied facing. Proclad, black. Vägledning för specifikationsalternativ: Optional factory-applied facing. Proclad, white. Vägledning för specifikationsalternativ: Optional factory-applied facing. |
Items to be insulated | Vägledning för specifikationsalternativ: Insert requirements. |
Nominal density | 40 kg/m³. |
Thermal conductivity at 10°C (maximum) | To EN 12667, 0.025 W/m·K. |
TemperatureRange | -50°C to +120°C. |
CompressiveStrength | To EN 826, 120 kPa (minimum). Tillverkarens vägledningParallel to rise. |
Closed cell content | To EN 4590, ≥90%. |
Dimensional stability | To EN 1604, ≤1.5%. |
Water absorption | To EN 1609, ≤1.25 kg/m². |
NBS LCA hjälper byggproffs att mäta miljöpåverkan och identifiera produkter med låga koldioxidutsläpp för mer hållbara projekt.

Material | Phenolic foam |
| Carbon dioxide equivalent | |
Koldioxidekvivalent, enligt definition i BS EN 15804 Certifierad | |
Steg Normaliserad enhet (kg CO₂ eq/kg) Deklarerad enhet (kg CO₂ eq/kg) Steg:A1–A3 (”Produktionsskede”) Normaliserad enhet :11.7 (kg CO₂ eq/kg) Deklarerad enhet :11.7 Värdevägledning: A1-A3
| |