White
Verifierad av tillverkaren för 4 månader sedan
UL-EU Certified
Certifikattyp
EPD
Certifikattyp
Encasement system using non-combustible mineral bound light weight boards. Two-sided beam protection 600–1200 mm deep; board to framed casing fix.
Steelwork protection.
PROMAT PROMATECT®-250 is a non-combustible mineral bound light weight board and provides a high degree of strength and dimensional stability and fire protection to structural steel and is suitable for areas where the relative humidity is up to 85%.
It is classified A1 non-combustible according to BS EN 13501-1.
Features and benefits:
Färg | White |
ytbehandling | Smooth Vägledning för specifikationsalternativ: One face, ready to form a finished surface. Sanded Vägledning för specifikationsalternativ: Reverse face. |
Material | Calcium silicate Vägledning för specifikationsalternativ: Autoclaved calcium silicate spheres bound in a mineral matrix. |
Form | Rectangle |
Längd | Bespoke |
Bredd | Bespoke |
Höjd | Bespoke |
Garantibeskrivning | Tillverkarens vägledningEtex Building Performance Limited warrants that its products and component parts shall be durable and free from defects due to faulty manufacturing or factory workmanship. Etex Building Performance Limited also warrants that, when combined to form a system as detailed in the Project Pack specification document including associated CAD drawings and any other specific technical recommendations made in relation to this project, will meet the specified system performance. The full details of this warranty are covered in the Promat Warranty Document, available upon request. |
Uniclass | |
CAWS | K11/54 Fire protection board K11/885 Fire protection board |
Klassificeringsdata | |
Support | 30 x 52 x 30 x 0.5 mm steel U-track and 36 x 50 x 34 x 0.5 mm steel C-studs. Z-section 25 x 25 x 25 x 1.2 mm. Fixings: 3.7 x 16 mm shot-fire nails or M4.2 x 12 mm wafer head screws. Vägledning för specifikationsalternativ: Casings are installed using a metal frame consisting of U-track channels fixed to the underside of the top flange and the upper side of the bottom flange of the steel beam. Vertical steel channels are fitted into the horizontal channels at 1250 mm maximum centres. Where the beam abuts a concrete or blockwork wall, install Z-section 25 x 25 x 25 x 1.2 mm to the bottom flange, running parallel to the wall. Fixings: maximum 300 mm centres. Tillverkarens vägledningFor beam widths over 325 mm, use minimum 25 x 25 x 1.2 mm Z-sections at maximum 610 mm centres perpendicular to the wall to support soffit boards, fixed with 3.7 x 16 mm shot-fire nails or M4 x 9.5 mm pan head screws at maximum 300 mm centres. |
Insulation | Low density (10–30 kg/m³) glass mineral wool. Vägledning för specifikationsalternativ: If required for acoustic or thermal performance. Not required. |
Linings | Inner and outer layers: PROMATECT®-250 board thickness determined by section factor (A/V), fire resistance period and limiting steel temperature. Maximum board length 1250 mm. Vägledning för specifikationsalternativ: Minimum PROMAT PROMATECT®-250 thickness for compartmentation either side of steel: 60 minutes: 15 mm; 90 minutes: 20 mm; 120 minutes; 25 mm. Where protection to the structural steel and compartmentation are required, thicker of the two boards should be used. For two-sided protection where compartmentation is also required, a double layered encasement must be installed: 2 x 15 mm for 60 minutes, 2 x 20 mm for 90 minutes or 2 x 25 mm for 120 minutes. Tillverkarens vägledning
|
Fasteners | Fixing to metal track and stud: M3.5 CSK Self Tapping Screws. Fixing to board edge and coverstrips: Chisel point staples minimum 35 x 12 x 1.6 mm (50 x 12 x 1.6 mm for board thicknesses over 15 mm). Vägledning för specifikationsalternativ:
|
System accessories | FSi Promat Pyrocoustic® Fire Resistant Sealant. |
Brandmotstånd | Vägledning för specifikationsalternativ: Fire resistance (minutes) to EN 13501-2. Insert requirements. |
Colour/ Finish | Vägledning för specifikationsalternativ: Insert requirements. Tillverkarens vägledningDecorative finishes should be applied in accordance with Promat Technical Data Sheet TDS 056 (https://www.promat.com/en-gb/construction/documentation/). |
Section factor | Maximum 350 m-1. |
Steel sections | 600–1200 mm deep and 325 mm maximum width. |
Strips | Coverstrips: Thickest encasement board layer x 100 mm wide PROMAT PROMATECT®-250 coverstrips fitted behind board joints and at the start and end of the beam. Vägledning för specifikationsalternativ: Coverstrips are not required to the top or bottom flanges of beam encasements. Coverstrips are not required for double layer encasements. |
Third-party certification | As detailed in UL-EU Certificate No. UL-EU-01220a-CPR. Vägledning för specifikationsalternativ: Note: Depending on site conditions, alternative fixing methods may be required for beams and columns, one- or two-sided exposure or interface with other building elements. These fixing methods are outside the scope of current EN test methods. These recommendations are based on the principles of EN 13381-4 and given in good faith. They should be approved by the responsible designer or through independent third party assessment. |
Installation | A nominal 3 mm gap must be left between the edge of the PROMAT PROMATECT®-250 board and the solid wall. This gap must be filled with FSi Promat Pyrocoustic® Fire Resistant Sealant. |
NBS LCA hjälper byggproffs att mäta miljöpåverkan och identifiera produkter med låga koldioxidutsläpp för mer hållbara projekt.

Materialets ursprungsland | Belgium |
Produktens tillverkningsland | Belgium Tillverkarens vägledningApplies to the bulk board material only. Other components are from other countries. Consult manufacturer for details. |
Material | Calcium silicate Vägledning för specifikationsalternativ: Autoclaved calcium silicate spheres bound in a mineral matrix. |
| Carbon dioxide equivalent | |
Koldioxidekvivalent, enligt definition i BS EN 15804 Certifierad | |
Steg Normaliserad enhet Deklarerad enhet (kg CO₂ eq/unit) Steg:A1–A3 (”Produktionsskede”) Normaliserad enhet : Deklarerad enhet :- Tillverkarens vägledningLatest EPD information available at: https://www.promat.com/en-gb/document-request/pi369182/PROMATECT-250 EPD_pdf/ | |
Återvinningsbarhet | Gypsum, calcium silicate and metal components can be recycled depending on the segregation of all materials. |
Promat - PROMATECT®-LS - Cable Protection - CP LS-001S
Promat - PROMATECT®-LS - Service Enclosure - SE LS-001S
Promat CS PXS-30-90-001S - PROMATECT®-XS - Concrete Slab Fire Protection System
Promat PROMATECT®-XS Structural Steel Protection ST PXS-005S - Three Sided Beam Encasement System
Promat PROMATECT®-XS Structural Steel Protection ST PXS-007S - Four Sided Beam Encasement System
Promat PROMATECT®-XS Structural Steel Protection ST PXS-008S - Four Sided Column Encasement System
Promat VERMICULUX®-S - Encasements - ST VLUX-209S
Promat VERMICULUX®-S - Encasements - ST VLUX-210S
Promat VERMICULUX®-S - Encasements - ST VLUX-213S
Promat VERMICULUX®-S - Encasements - ST VLUX-214S