Verifierad av tillverkaren för 5 månader sedan
KIWA BDA
Certifikattyp
Certifire Certificate
Certifikattyp
With 180 minutes integrity (E) and 90 radiance (EW), the FireMaster® Plus² fire curtain provides fire safety whilst blending seamlessly and discreetly into ceilings and building design.
An electrically operated active fire curtain barrier assembly. Active fire curtain barrier assemblies comprises a woven steel and glass fabric wound on to a steel roller, powered by an internal 24 V d.c. electric motor, enclosed within a 1.2 mm-thick steel box. A bottom bar is fitted to the bottom edge of the curtain providing tension to the curtain with sufficient weight for the curtain to ‘fail-safe by gravity’.
The 24 V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position. Has been tested to the requirements of BS EN 14600:2005 for ‘Durability of Self-Closing’ (500 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.08 m/s). Has been tested to the requirements of BS EN 1634-1:2014 for ‘Fire Resistance’ (180 minutes integrity). Has been tested to the requirements of BS EN 1634-1:2014 for ‘Radiant Heat Flux’ (90 minutes).
Operation:
Active fire curtain barrier assemblies commence movement upon initiation of alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function. Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.
In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. At the end of the period, the barrier assembly will deploy.
Fire resistance:
180 minutes (3 hours) integrity.
Period of radiation:
107 minutes <15 kW/m².
Classification:
E180 EW90 C0 (single).
Product certification, performance and/ or testing:
Approving standards:
The following standards apply to this product:
Färg | Other |
ytbehandling | Galvanized |
Material | Steel Fabric Vägledning för specifikationsalternativ: Glass fabric. |
Form | Rectangle |
Längd | Bespoke |
Bredd | Bespoke |
Höjd | Bespoke |
Garantibeskrivning | One year Vägledning för specifikationsalternativ: From date of commissioning. |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
SKU Code | FireMaster Plus Fire Curtain |
Klassificeringsdata | |
Standards | BS 8524‑1, BS EN 1634‑1, BS EN 1634‑3, BS EN 1363‑1, BS EN 1363‑2, BS EN 13501‑2 +A1, BS EN 14600, BS 476‑6:1989+A1, BS 476‑7, BS EN ISO 14184‑1, BS 6323‑5:1982, BS EN ISO 9001:2008, BS EN ISO 14001:2004, ISO Guide 65, BS EN ISO 17065, BS EN 1634‑3, BS 8524‑1, BS 5234‑2, BS EN 14600. |
Barrier assemblies | To BS 8524-1. |
Test standards | Vertical, horizontal and angled to BS EN 1634-1. |
Third-party certification | Certified by IFCC Ltd. |
Size | Bespoke. Vägledning för specifikationsalternativ: Insert requirement. |
Performance | |
Pressure and impact | Vägledning för specifikationsalternativ: As per BS 8524, impact and pressure tested as large soft body impact and crowd pressure in accordance with BS 5234-2. |
Durability class | C1. Vägledning för specifikationsalternativ: C1 - 500 cycles tested, as per BS 8524 Annex D, "Durability of self-closing". |
Smoke containment | Not required. Required. Vägledning för specifikationsalternativ: Option available under BS EN 1634-3. |
Fire resistance | E180 Integrity; EW90 Radiation. |
Reaction to fire | Vägledning för specifikationsalternativ: Fabric used in the construction of a barrier assembly shall be tested in accordance with BS 476-6 and BS 476-7 to achieve a Class 0 or Class 1 rating, or BS EN ISO 1716 or BS EN ISO 1182 and BS EN 13823 to achieve a minimum of B-s3,d2 (Class 0 equivalent) or a minimum of C-s3,d2 (Class 1 equivalent). |
Barrier units | Single. Overlapped. Multiple. Vertical. Tillverkarens vägledningFlexible metallic fabric.
|
Deployment | Full. Fire alarm system active. Local detector active. Thermal activation. Delayed. Partial deploy. Controlled decent. Gravity fail safe deployment. |
Activation | Commences movement upon initiation of alarm or power or system failure. |
Accessories | None. Beam protection and obstruction warning. Vägledning för specifikationsalternativ: Will sound in the event of an obstruction being placed at the barrier drop line. Emergency retract. Vägledning för specifikationsalternativ: Touch-button retract facility for multi-escape. Split drop delay. Vägledning för specifikationsalternativ: Will partially deploy to pre-determined level to permit escape. Visual alert system. Vägledning för specifikationsalternativ: Light warning system. Voice warning. Vägledning för specifikationsalternativ: Auto-spoken multi-message facility. Emergency egress buttons. Emergency access buttons. Obstruction warning system. Audible visual warning systems. Remote test switches. Heat and smoke detectors. Building management system. Split drop delay. |
Classification | E180 EW90 C1, BS 8524. |
Frame colour/ finish | Galvanized Steel. Steel. Polyester powder-coated, RAL 9017. Polyester powder-coated, RAL 9010. Polyester powder-coated, RAL. Vägledning för specifikationsalternativ: Insert requirement. |
Innehåller Red List-material | No |
Materialets ursprungsland | United Kingdom |
Produktens tillverkningsland | United Kingdom |
Material | Steel Fabric Vägledning för specifikationsalternativ: Glass fabric. |
| Carbon dioxide equivalent | |
Koldioxidekvivalent, enligt definition i BS EN 15804 Självdeklarerad | |
Steg Normaliserad enhet (kg CO₂ eq/kg) Deklarerad enhet (kg CO₂ eq/kg) Steg:A1–A3 (”Produktionsskede”) Normaliserad enhet :285 (kg CO₂ eq/kg) Deklarerad enhet :285 Tillverkarens vägledning285.92 tCO2e for yearly emissions | |
Återvinningsbarhet | Coopers Fire offer a take back service where product is broken down into component parts. Metal = recycled Fabric = recycled WEEE = disposed through correct channels |
Återvunnet innehåll | 0 % |
Förväntat liv | Ten year Tillverkarens vägledningProduct has been cycle tested 500 times which equates to roughly 10 years worth of use. With regular service and maintenance the life can be expected to be longer than this. |
Detta BIM-objekt har skapats för att uppfylla kraven i
Läs mer om
| Plattform | Kompatibel | Version |
|---|---|---|
| - | 1 | |
Revit 2017 | 1 |
Blavatnik School of Government, University of Oxford. Bespoke Fire Curtains and Smoke Curtains
Harris Calnan Construction Company (HCCC) - FireMaster Fire Curtains
HOTEL RUSSELL, LONDON, UK
The SSE Hydro, Glasgow. Fire Curtains and Smoke Curtains
Fire Curtains Merging Safety with Luxury Interiors – Aston Villa Fire Curtain Design
Fire Curtain - FireMaster® A1 - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers
Fire Curtain - FireMaster® A1 ResQ-Window for Fire Curtain. - Fire Curtain Vision Panel
Fire Curtain - FireMaster® Concertina Closed - Rectangular - Concertina Fire Curtain - Concertina Vertical Fire Curtain
Fire Curtain - FireMaster® Concertina Open - L Shape - Concertina Fire Curtain - Fire Curtain Concertina
Fire Curtain - FireMaster® Concertina Open - Rectangular - Concertina Fire Curtain - Fire Curtain Vertical Concertina
Fire Curtain - FireMaster® Concertina™ Closed - Circular - Concertina Fire Curtain - Concertina Vertical Fire Curtain
Fire Curtain - FireMaster® Concertina™ Open - Circular - Concertina Fire Curtain - Fire Curtain Vertical Concertina
Fire Curtain - Vii Fire i-Zone - Vertical Active Fire Curtain - Vertical Fire Curtain
Fire Curtain FireMaster® 4/1000 - Vertical Active Fire Curtain - Vertical Fire Curtain
Fire Curtain Vii® Fire A1 - Vertical Active Fire Curtain - Vertical Fire Curtain