QA Certificate
Certificate type
Electronically controlled heat interface unit.
For domestic applications.
Electronically controlled twin plate hydraulic heat interface unit (HIU), designed to provide instantaneous hot water and heating to the dwelling.
Features and benefits:
Application:
For domestic applications.
Finish | Matt Textured |
Color | Black or Grey |
Features | WRAS Approved, Domestic hot water (DHW) output up to 60 kW, heating (HTG) output up to 10 kW, DHW and HTG controlled by PICV’s |
Material | Pipes, fittings, valves (primary and heating): 1.4301 (AISI 304), CW617N, CW614N, CW602N, CW625N, GG15, Pipes, fittings, valves (domestic hot water): 1.4404 (AISI 316L), CW617N, CW617N, CW602N, Heat exchanger: 1.4404 (AISI 316L) Cu Brazing, Insulation: Expanded polypropylene (EPP), |
Shape | Rectangular |
Size | 530 x 690 x 250 mm (l x h x d) |
WarrantyDescription | Supply of replacement parts only |
Uniclass 2015 |
Product Reference | vTherm°e StandardvTherm°e With Insulated Valve RailHelps minimize losses. vTherm°e With Insulated Valve Rail And Pipe BracketAllows for up and down connection. |
Standard | CE, BESA, WRAS |
Duty | - |
Primary flow temperature | 60–90°C |
Primary return temperature | 70°C Primary Flow = 27.9°C; 60°C Primary Flow = 29°C (Volume-Weighted Average Return Temperatures (VWART)) |
Pressure drop | <50 kPa (primary side), <10 kPa (heating) |
Flow rate | 0.32 L/s |
Heating supply temperature | Maximum 80°C |
Hot water supply temperature | Maximum 60°C |
Casing | Fully insulated EPP casing |
Insulation | Expanded polypropylene |
Components | - |
Primary | Manufacturer's standard |
Secondary | Manufacturer's standard |
Controls | Electronically controlled. The HIU controller shall utilize the secondary side DHW and heating temperatures to control Pressure Independent Control Valves (PICVs) located on the primary side of both plate heat exchangers to maintain the temperature. A keep warm function maintains a primary flow temperature at the unit |
Overall sound power level | 31.8 dB |
Weight | 30 kg (dry), 35 kg (wet) |
Electrical requirements | 230 V, 5 A (50 Hz)Maximum power consumption: 60 W. |
Accessories/ Other requirements | NoneApartment weather compensationBluetoothFlushing bypass assemblyIntelligent data collectionM-BusModbusRadioRJ45Wi-FiNBIoT |
Performance | - |
Hot water system (HWS) capacity (minimum) | 60 kW |
Heating capacity (minimum) | 10 kW |
HWS temperature | 55°C |
Heating secondary flow temperature (UFH) | 45°C |
Heating secondary return temperature (UFH) | 35°C |
Heating secondary flow temperature (Radiators) | 60°C |
Heating secondary return temperature (Radiators) | 40°C |
HIU primary pressure rating | 10 barStandard. 16 barOn request. |
Maximum HIU primary differential pressure | 4 bar |
Maximum secondary heating working pressure: | 2.5 bar |
Secondary heating safety relief valve pressure | 3 bar |
Maximum secondary main cold water (MCW)/ domestic hot water (DHW) pressure | 10 bar |
Minimum MCW pressure | 1 bar |
Colour | BlackGrey |
Finish | MattTextured |
Standard product features | Colour: Black or grey. Features: WRAS approved, Domestic hot water (DHW) output up to 60 kW, heating (HTG) output up to 10 kW, DHW and HTG controlled by PICVs. Finish: Matt or textured. Material:
Some additional materials are used by component manufacturers such as valves and pumps. These are in small components within the assembly. Shape: Rectangular. Size: 530 x 690 x 250 mm (l x h x d). Warranty description: One year from date of commissioning on replacement parts only. Recyclability: 90%+ of weight. Red listed materials: PVC in some cables. Country of origin: Several European countries including Denmark, Germany and Switzerland. Country of manufacture: Final assembly undertaken in the UK. |
Recyclability | 90%+ of weight |
Platform | Compatible | Version | Certified to |
---|---|---|---|
![]() | - | 1 | 2.1 |
![]() | - | 1 | 2.1 |