NBS Source
I'm a manufacturer

Talkback Damper-Shutter Control System

Verified by manufacturer today

Lorient

Smoke damper/ shutter assembly to prevent the passage of cold smoke.

Jump to:
+44 (0)1626 834252 Website

Application

Smoke Control Shutter System. Provides Fire & Smoke resistance in conjunction with Intumescent Air Transfer Grille. Doors, panels, walls + ducts: effective for cold smoke.

Description

A smoke damper/ shutter assembly for use in conjunction with Lorient intumescent air transfer grilles to prevent the passage of cold smoke which can be equally dangerous.


The Talkback system has been designed to control up to sixteen damper/ shutter assemblies from one centralised, status monitoring unit. A unique two-way communication system operates between the Damper Control and Monitor Unit (DCM) and each damper/ shutter actuator connected to the system.


This monitoring unit allows all the damper/ shutter assemblies to be quickly and visually checked to identify and locate any defective shutters.


Features and benefits:

  • Fail-safe – the dampers/ shutters will automatically close in the event of an alarm, power failure or damage to the wiring.
  • Resets automatically – when the alarm is cancelled or power restored.
  • Self-testing – every 24 hours the dampers/ shutters are automatically closed and opened to check they are working and to dislodge any dust and debris between the moving parts.
  • Continuously monitors the status of each damper/ shutter and displays this on the DCM.
  • Easy and quick to install – simple loop wiring is used and the damper/ shutter units are supplied ready assembled and tested.
  • Uses a safe, low voltage DC supply to open and close the dampers/ shutters.
  • Successfully tested in accordance with the requirements of the Electro Magnetic Compatibility and Low Voltage Directive and therefore bears the CE mark.


Optional features:

  • Audio warning: An extra optional audio warning device (AMS) can be connected to the DCM wiring circuit. This device would be incorporated to draw attention to the DCM status display in the event of a fault occurring.
  • B.M.S monitoring: The Audio Monitor can be used to communicate with a BMS or fire panel. A no volt contact (normally open) is provided for within the AMS in order to provide a fault indicator to the BMS.
  • Battery back up: The DCM incorporates a connection for a battery back up option. An appropriate re-chargeable battery and enclosure is available from Lorient if required.

General information

Color

Cream

Shape

Other

Length

125 mm

Width

165 mm

Height

155 mm

Uniclass

Pr_65_65_24_78 Shut-off dampersPrimary

CAWS

U90/440 Dampers, automatic

U90/443 Dampers, fire and smoke

U90/440 Dampers, fusible link type

U90/443 Dampers, fire/ smoke

Specification data - Shut-off dampers

Control method

Electric and electronic.

Third-party certification

CE marked.

Sustainability data

Country of product manufacture

United Kingdom