SUPALUX®
Compare variants

Application

Promat can provide a design and specification advisory service, including advice on the suitability of these boards for the proposed application and it is recommended that they be consulted early in the design process.

Description

Non-combustible reinforced calcium silicate fire protection board.


Features and benefits:

  • Reinforced with selected fibres and fillers.
  • Resistant to the effects of moisture and will not physically deteriorate when used in damp or humid conditions.
  • Fire protection board.
  • Boards are either butt jointed or flush jointed.

General information

Finish

Smooth finish on one face with a sanded reverse face.

Material

A non-combustible calcium silicate board reinforced with selected fibres and fillers. It is formulated without inorganic fibres and does not contain formaldehyde.

Shape

Square

Square profile.

Size

2440 x 1220 mm

WarrantyDescription

Etex Building Performance Limited warrants that our passive fire protection products and component parts, when installed in the building originally designed, built and unaltered in accordance with the conditions and procedures set out in Promat Passive Fire Protection Handbook, this specification document and associated CAD drawings; and any specific technical recommendations made in relation to the above project, shall be durable and free from defects due to faulty manufacturing or factory workmanship. The system must be installed by a 3rd party accredited fire protection contractor, and where included in the specification, solely with proprietary products and components as supplied by Etex Building Performance Limited. The scope of this warranty will be dependent on the application and the environment in which the products are being installed.

Uniclass 2015

Pr_25_71_80_23 Fibre-reinforced calcium silicate boardsPrimary

CAWS

G20/950 Fascias/ barges/ soffits

G20/99 Fascias/ barges/ soffits

K11/60 Board

K11/795 Wall lining on metal framing

K11/885 Fire protection board

K40/270 Boards

U90/425 Rigid ductwork and fittings

U90/425 Rigid ductwork and fittings

U90/490 Site-applied insulation to ductwork

U90/490 Site-applied insulation to ductwork

Specification data - Fibre-reinforced calcium silicate boards Enhanced data

Standard

To BS EN 12467.

In accordance with the criteria of BS 476: Part 22: 1987.

Reaction to fire class

Class 1 Surface Spread of Flame to BS 476-7: 1987, Class 0 Surface to Building Regulations Approved Document B.

Sheet size

2440 x 1220 mm.

Thickness

6 mm.

9 mm.

12 mm.

15 mm.

Edges

Square.

Finish as delivered

Painted.

Paint finishes should not compromise the surface spread of flame. Finishes should be applied in accordance with Promat TDS 056.

Untreated.

Colour

Off-white.

Product Reference

SUPALUX®

Reaction to fire classification

Non-combustible with a reaction to fire Classification of A1 according to BS EN:13501-1.

Nominal dry density

950 kg/m³.

Form

Steelwork encasements, floors, roofs, ceilings, partitions, service enclosure.

ThermalConductivity

0.17 at 20°C/ W/mK.

Fire performance

30-240 minutes.

Up to 240 minutes depending on system and application.

Accessories

None.

Promat Moisture Resistant Joint Filler.

Use to fill joint and screw holes with and sand to a smooth flat surface.

Environmental information

Contains Red List materials

No

Country of product manufacture

China

Recyclability

Recyclable as crushed aggregate.

Literature

The Passive Fire Protection Handbook: Chapter 2 - User Guide

The Passive Fire Protection Handbook: Chapter 2 - User Guide

The Passive Fire Protection Handbook: Chapter 4 - Ceilings, Floors and Roofs

The Passive Fire Protection Handbook: Chapter 4 - Ceilings, Floors and Roofs

The Passive Fire Protection Handbook: Chapter 5 - Partitions and External Walls

The Passive Fire Protection Handbook: Chapter 5 - Partitions and External Walls

The Passive Fire Protection Handbook: Chapter 6 - Fire Rated Ductwork

The Passive Fire Protection Handbook: Chapter 6 - Fire Rated Ductwork

The Passive Fire Protection Handbook: Chapter 8 - Smoke Barriers and Doors

The Passive Fire Protection Handbook: Chapter 8 - Smoke Barriers and Doors

Promat Supalux self supporting ceiling access from below 120 minutes (TDS111)

Promat Supalux self supporting ceiling access from below 120 minutes (TDS111)

Supalux self supporting ceiling access from below 60 minutes (TDS110)

Supalux self supporting ceiling access from below 60 minutes (TDS110)

Similar products from Promat UK

Promat TL Board®

Promat TL Board®

PROMATECT®-L500

PROMATECT®-L500

Vermiculux® - S

Vermiculux® - S