SmokeStop Concertina™ Closed - Rectangular - Concertina Smoke Curtain

Verified by manufacturer 6 months ago

Coopers Fire Ltd

A multi-side smoke curtain that has been developed to provide high performance smoke protection to EN 12101-1.

Jump to:
BIM object icon
+44 (0)23 9245 4405 Website

Application

An electrically operated active smoke barrier used to form a virtually continuous barrier against fire effluent.

Description

An electrically operated active smoke barrier assembly. Active smoke barrier assemblies comprises a metallic fabric, fan-folded and retained in a metal tray, powered by an internal 24 V d.c. electric motor, enclosed within a 1.2 mm-thick steel box. A special bottom tray is fitted to the bottom of the curtain providing tension to the curtain with sufficient weight for the curtain to ‘fail-safe by gravity’.


The edges of the curtain are retained inside side guides, providing pressure resistance of 20 Pa. The 24 V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position. Active smoke curtain barrier assemblies have been tested to the requirements of EN 12101-1, Annex B for ‘Reliability and response times’ (1000 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.07 m/s). Active smoke curtain barrier assemblies have been tested to the requirements of EN 12101-1 for ‘Temperature/ time resistance’ (120 minutes integrity). The fabric used in active smoke curtain barrier assemblies have a reaction to Fire Classification of ‘A1’.


Operation:

Active smoke curtain barrier assemblies commence movement upon initiation of alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function. Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.


In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. At the end of the period, the barrier assembly will deploy.


Period of fire resistance:

60 minutes (1 hour) integrity.


Classification:

DH60, A1.


Product certification, performance and/ or testing:

  • Complete active smoke barrier assemblies are CE marked in accordance with EU Construction Products Directive (89/106/EEC).
  • Active smoke barrier assemblies are certified by an independent accredited certification body operating to ISO/ IEC 17065:2012.
  • Complete active smoke barrier assemblies have been fully tested to BS EN 12101-1+A1.
  • Motor(s) used within active smoke barrier assemblies in the above tests have been tested for operation at temperatures of 400°C as required by BS 8524-1.
  • The fabric used within active smoke barrier assemblies have been tested to BS EN ISO 1716.
  • The fabric used within active smoke barrier assemblies have been tested to BS 476 pt 6 & pt 7.
  • The fabric used within active smoke barrier assemblies have been tested to BS EN 13823.
  • The fabric used within active smoke barrier assemblies have been tested to BS 6853.


Approving standards:

The following standards apply to this product:

  • BS EN 12101-1:2005+A1:2006, Smoke and heat control systems – Part 1: Specification for smoke barriers.
  • BS EN 1363-1:2012, Fire resistance tests – Part 1: General requirements.
  • BS EN 1634-3, Fire resistance tests for door and shutter assemblies – Part 3: Smoke control doors and shutters.
  • BS EN 13501-4:2007+A1:2009, Fire classification of construction products and building elements. Classification using data from fire resistance tests on components of smoke control systems.
  • BS EN ISO 1716:2010, Reaction to fire tests for products. Determination of the gross heat of combustion (Calorific value).
  • BS EN 13823:2010, Reaction to fire tests for building products. Building products excluding floorings exposed to the thermal attack by a single burning item.
  • BS EN 13501-1:2007+A1:2009, Fire classification of construction products and building elements. Classification using test data from reaction to fire tests.
  • BS 476-6:1989+A1:2009, Fire tests on building materials and structures. Method of test for fire propagation for products.
  • BS 476-7:1997, Fire tests on building materials and structures. Method of test to determine the classification of the surface spread of flame of products.
  • BS EN ISO 9001:2008, Quality management system.
  • BS EN ISO 14001:2004, Environmental management system.

General information

Color

Other

Finish

Galvanized

Powder-coated

Material

Fabric

Shape

Rectangle

Width

Bespoke

Height

Bespoke

Warranty description

One year

Guidance for specification option:

From date of commissioning.

Uniclass

Pr_25_80_79_01 Active smoke barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Active smoke barriers

Standard

BS EN 12101-1:2005+A1:2006, BS EN 1363-1:1999, BS EN 1634-3, BS EN 13501-4:2007+A1:2009, BS EN ISO 1716:2010, BS EN 13823:2010, BS EN 13501-1:2007+A1:2009, BS 476-6:1989+A1:2009, BS 476-7:1997, BS 6323-5:1982.

Classification categories

DH60, A1.

Material

Flexible metallic fabric.

Guidance for specification option:

  • The main curtain fabric type is EFP™ A1, which is a stainless steel wire reinforced glass fabric fire barrier. It has an area weight of 665 g/m² -5%, + 10%.
  • The curtain fabric offers dimensional stability and is non-combustible to BS EN 13501-1 + A1– Reaction to Fire.
  • The fabric has passed testing to BS 476-6 (Method of test for fire propagation for products).
  • The fabric has passed testing to BS 476-7 (Method of test to determine the classification of the surface spread of flame for products).
  • The fabric has passed testing to BS EN 1634-1, BS EN 1363-1, BS EN 1362-2 and BS EN 1634-3 (Fire/Smoke Resistance)
  • The fabric has passed testing to BS EN ISO 1716 (Determination of the Heat of Combustion for Building Products).
  • The fabric has passed testing to BS EN 13823 (Reaction to Fire Tests – Single Burning Item)
  • The fabric has passed testing to HSG 248 (Analysis of Material for the presence of Asbestos).
  • The fabric has passed testing to BS EN 14184-1 (Textiles – Determination of Formaldehyde – Part 1: Free and hydrolysed formaldehyde (water extraction method).

Opening sizes

Guidance for specification option:

Insert requirement.

Accessories

None.

Beam protection and obstruction warning.

Emergency retract.

Split drop delay.

Visual alert system.

Show more

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Recyclability

Coopers Fire offer a take back service where product is broken down into component parts.
Metal = recycled
Fabric = recycled
WEEE = disposed through correct channels

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

0 %

BIM objects

BIM object icon

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
IFC
-

2

Revit

Revit 2017

2

Literature

Examples of FireMaster and SmokeStop Concertina Installations

Examples of FireMaster and SmokeStop Concertina Installations

Similar products from Coopers Fire Ltd

SmokeStop Concertina™ Closed - Circular - Concertina Smoke Curtain

SmokeStop Concertina™ Closed - Circular - Concertina Smoke Curtain

SmokeStop Concertina™ Open - Circular - Concertina Smoke Curtain

SmokeStop Concertina™ Open - Circular - Concertina Smoke Curtain

SmokeStop Concertina™ Open - L Shape - Concertina Smoke Curtain

SmokeStop Concertina™ Open - L Shape - Concertina Smoke Curtain

SmokeStop Concertina™ Open - Rectangular - Concertina Smoke Curtain

SmokeStop Concertina™ Open - Rectangular - Concertina Smoke Curtain