NBS Source
I'm a manufacturer
Compare variants

RockLap H&V Pipe Section - Insulation

Verified by manufacturer 14 days ago

20 mm

ROCKWOOL Ltd Variant:

Preformed pipe insulation for thermal, acoustic and fire stopping applications.

Jump to:
+44 (0)1656 862621 Website

Application

Preformed pipe insulation for thermal and fire stopping insulation to HVAC pipework.

Suitable for heating and ventilation pipes in a range of settings, through buildings, plants and other structures.

Description

ROCKWOOL H&V Pipe Sections have been successfully tested for providing fire stopping to steel and copper pipe penetrations where they penetrate fire resistant walls and floors.

Suitable for heating and ventilation pipes in a range of settings, through buildings, plants and other structures.


Features and benefits:

  • Fast and simple to install with the snap system, reducing cost and the amount of time on site.
  • The requirement for taping is significantly reduced due to the security of the snap system, taping is simply used as a seal.
  • ROCKWOOL RockLap H&V Sections have limited combustibility; the surface finish is also compliant with Class 0.
  • The sections are resilient and high performing provided in a one-piece, with reinforced foil and integral lap.
  • CE marked in accordance with BS EN 14303.


Resistance to fire performance:

Tested to BS EN 1366-3, for the fire resistance of penetration seals offering up to EI 120.

General information

Color

Silver

Material

Stone wool

Length

1000 mm

Height

20 mm

25 mm

30 mm

35 mm

40 mm

Show more

Uniclass

Pr_80_77_76_54 Mineral wool pipe section insulationPrimary

CAWS

S90/570 Insulation to pipelines

T90/450 Insulation to pipelines to control heat loss

Specification data - Mineral wool pipe section insulation

Standard

To BS EN 14303, ISO 14001.

Thermal conductivity

0.033–0.034 W/m·K.

Finish

Aluminium foil faced.

Reaction to fire classification

A2-s1,d0.

Insulation thickness (minimum)

20 mm.

Execution

Installing foil faced mineral wool insulation on pipelines.

Pipe diameter

-

Manufacturer guidance

Insert requirements, 17–406 mm.

Refer to manufacturer's literature for sizing information.

Specific heat

0.84 kJ/kg·K (nominal) at 20°C.

Density

120 kg/m³.

Length

1000 mm.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Recyclability

Can be recycled

Manufacturer guidance

ROCKWOOL is recyclable. For waste ROCKWOOL material that may be generated during installation or at end of life, the manufacturer is happy to discuss the individual requirements of contractors and users considering returning these materials to their factory for recycling.

Case studies

Morriston Hospital

Morriston Hospital

Aldgate Tower

Aldgate Tower

Similar products from ROCKWOOL Ltd

ROCKWOOL® Techtube - Pipe insulation

ROCKWOOL® Techtube - Pipe insulation