As part of the comprehensive FIREPRO range of fire protection products, ROCKWOOL Intumescent Pillows have been tested to BS 476: part 20 to provide up to 4 hours fire protection to metal services and cables passing through fire resisting compartment floors and walls.

Intumescent Pillows are simply packed tightly in between penetrating services and the wall. In a floor, pillows are additionally supported by means of a mesh support system.

Under fire conditions, Intumescent Pillows expand several times their original volume to form an effective seal around service penetrations.

Intumescent Pillows are suitable for use with:

  • Metal pipework.
  • Cable trays.
  • Electrical trunking (inside and outside).

Advantages:

  • Simple to install.
  • Easy to remove and reinstate whilst changing services.
  • Maintenance free.
  • Dry system.
  • Available from 48 hours of order.

General information
Specification data
Product Reference

ROCKWOOL Intumescent Pillows

Thickness

35 mm

Width

50 mm

100 mm

150 mm

200 mm

Length

300 mm

Accessories

Galvanised steel mesh

2.5 mm wire diameter. (Not supplied by ROCKWOOL).

Standard product features

Performance:

Will provide 4 hours fire integrity and 2 hours insulation rating as tested in accordance with BS 476-20.