NBS Source
I'm a manufacturer

Plafotherm® GK HEKDA

Verified by manufacturer 2 months ago

Lindner Group

Heated and chilled plasterboard ceiling.

Jump to:
BIM object icon
02082466333 Website

Application

For ceiling applications.

Description

Heated and chilled plasterboard ceilings with a heat conducting profile as a secondary grid.


This cost-effective system enables jointless surfaces – a multitude of plain or perforated panellings are available. All components are tested as a complete system and provide for best comfort and a pleasant room climate. The profile fuses with the substructure as constructive element and is screwed to the plasterboard panel.


The individual heated and chilled ceilings are connected in series (heating and cooling zones) until a pressure loss of approximately 25–30 kPa is achieved. The individual heating and cooling zones are connected parallel to the distribution pipe (regulation zone).


Features and benefits:

  • Can achieve a high occupancy rate of up to 100%, even in case of rooms with several ceiling fixtures.
  • Height differences and flexible shapes can be realized.
  • Six standard perforations available. Other perforations available on request. Consult manufacturer for perforation patterns.

General information

Finish

Plastisol

Material

Plasterboard

Shape

Rectangle

Other

Length

-

Manufacturer guidance

From 500–5000 mm.

Uniclass

Ss_30_25_22_51 Modular suspended ceiling systemsPrimary

CAWS

K40/10 Unit/ modular suspended ceilings

K40/115 Unit/ modular suspended ceiling system

Product range

Ceilings

Specification data - Modular suspended ceiling systems

Ceiling units

Plasterboard infill units.

Edges

Square.

Reaction to fire (to EN 13501-1)

A2-s1, d0 (non-combustible) / A1.

Guidance for specification option:

Panels / Substructure.

Coating

Plaster finish.

NominalCoolingCapacity

To EN 14240, 95.8 W/m².

Guidance for specification option:

10 K.

To EN 14240, 81.2 W/m².

Guidance for specification option:

15 K.

NominalHeatingCapacity

To EN 14037:2003, 108 W/m².

EN 14037:2003, 99.3 W/m².

Perforation pattern

6/18 R.

8/18 R.

10/23 R.

15/30 R.

8/12/50 R.

Show more

Ceiling type

Standard plasterboard building panels.

Plasterboard panel high-compressed.

Plasterboard panel with graphite share.

Length

-

Manufacturer guidance

Heat conducting profile (HCP): From 500–5000 mm. Insert requirement.

Profile width

150 mm.

250 mm.

Manufacturer guidance

Heat conducting profile (HCP)

BIM objects

BIM object icon

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

IFC
-

1

Similar products from Lindner Group

Baffle Ceilings

Baffle Ceilings

Canopy Ceilings

Canopy Ceilings

Cassette Ceilings

Cassette Ceilings

Corridor Ceilings

Corridor Ceilings

Expanded Metal Ceilings

Expanded Metal Ceilings

Fire rated metal ceilings

Fire rated metal ceilings

Hook-On Ceilings

Hook-On Ceilings

Post Cap Ceilings

Post Cap Ceilings