NBS Source
List your products
Newton Control Panel-Pro
Application

The Newton Control Panel-Pro will operate a maximum of two 750W/230V AC pumps. The panel is supplied with a vertical water level float switch and high water alarm float switch. The panel is designed to be used with an optional Newton Victron Battery Backup System, sized to suit the pumps and installed with sufficient battery power to ensure continued pumping during power outages.

Description

The Newton Control Panel-Pro is a pump control panel which has been designed to provide pump operation and diagnostics. The panel features interfaces for use with Newton battery backup and telemetry systems as well as connections to whole house alarm and monitoring systems.

The Control Panel PCB is split with two separate circuits, ensuring that pumping will continue even if one of the control circuits should fail. This effectively means that the Newton Control Panel-Pro is two control panels within one case, offering unrivalled redundancy.

Self-diagnostic programs test the pumps on a weekly basis to ensure correct pump performance, with the appointed service engineer automatically informed of any detected problem with either of the pumps if the Newton Dialer telemetry system is installed.

Features and benefits:

  • Automatic alternate duty cycle.
  • Has the ability to receive two totally independent power supplies; one from the mains, and one from a Victron Battery Backup System.
  • Alarm will sound upon detecting power failure.
  • Provides automatic electrical current monitoring for each pump, as well as automatic pump duty assist.
  • If the main float fails or becomes disconnected, the alarm float automatically takes over as the level control float.
  • An alarm checking signal is continually monitored to confirm the alarm float cables have been fitted correctly, not been tampered with or disconnected.
  • Each pump has a separate electronic circuit - this allows for one pump to continue operation if a fault develops.
  • Automatic testing of each pump every seven days.
  • 32 different alarm warning sounds are available.
  • Each pump is controlled by a zero-voltage solid state triac.
  • Each pump circuit has its own LCD display with a built-in flash memory.
  • Each pump has a manual override button and a reset button.
  • Supplied with a one-year back to base warranty which is dated from either the date of purchase or a proven date of installation - consult manufacturer for details.

For further information, please consult manufacturer.

Type:

- CP7:

When the Control Panel-Pro and the Dialer are supplied together, the panel is supplied with the Dialer already securely mounted within the panel. All power and trigger wiring is pre-connected and the Dialer is already programmed to receive the trigger information from the panel. The programmed triggers from the panel to the Dialer allow for the Dialer to give accurate information on a number of alarm occurrences within the panel, including water level high, pump requiring attention, or pump mains failure. Consult manufacturer for further details.

Application:

The Newton Control Panel-Pro will operate a maximum of two 750W/230V AC pumps. The panel is supplied with a vertical water level float switch and high water alarm float switch. The panel is designed to be used with an optional Newton Victron Battery Backup System, sized to suit the pumps and installed with sufficient battery power to ensure continued pumping during power outages.

General information

Features

Automatic alternate duty cycle, automatic testing of each pump every 7 days, automatic main float checking, automatic pump duty assist and an alarm on power failure - panel will alarm in the event of mains failure

Size

290 x 240 x 94 mm (or 17 mm if recessed into wall) (w x h x depth)

WarrantyDescription

The panel is supplied with a one-year back to base warranty which is dated from either the date of purchase or a proven date of installation. If the unit develops a fault during the warranty period, Newton Waterproofing Systems Ltd will repair or replace the unit under warranty. Contact the Newton sales office for a returns form which explains the returns procedure. The warranty will be invalidated if the unit is damaged because of improper handling, storage or installation, and in such cases a repair charge may be applicable

Uniclass 2015

Pr_70_55_76_62 Private packaged pumping stationsPrimary

CAWS

R12/135 Private packaged pumping stations and pressure pipeline system

R18/310 Private packaged pumping stations

Specification data - Private packaged pumping stations

Product Reference

Newton Control Panel Pro (CP2)

Newton Control Panel Pro and pre-fitted Newton Dialer (CP7)

Collection Tank type

Vertical

Pumps

-

Configuration

Pump control panel split with two separate circuits, ensuring that pumping will continue even if one of the control circuits should fail

Control

Pump control panel - Newton Control Panel-Pro is two control panels within one case

Integral accessories

The panel is supplied with a vertical water level float switch and high water alarm float switch

Weight

3.94kg

Power supply

230V (+ Battery Backup Option)

Sounder volume (dB)

94 dB

Switch type

Vertical (Pumps) and Reed (Alarm)

Power converter

MultiPlus 12/800/35 (BB1)

Battery backup facility for pumps of 150 W and 250 W.

MultiPlus 12/1200/50 (BB2)

Battery backup facility for pumps of 400 W.

MultiPlus 12/3000.120 (BB3)

Battery back-p facility for pumps of 750 W.

Quattro 12/3000/120 (BB4)

Battery backup facility for all pumps up to 750 W.

Standby batteries

60 Ah High Efficiency battery (BB20)

101 Ah High Efficiency battery (BB21)

201 Ah High Efficiency battery (BB22)

Standard product features

Colour:

Blue.

Features:

Automatic alternate duty cycle, automatic testing of each pump every 7 days, automatic main float checking, automatic pump duty assist and an alarm on power failure - panel will alarm in the event of mains failure.

Size:

290 x 240 x 94 mm (or 17 mm if recessed into wall) (w x h x depth).

Warranty description:

The panel is supplied with a one-year back to base warranty which is dated from either the date of purchase or a proven date of installation. If the unit develops a fault during the warranty period, Newton Waterproofing Systems Ltd will repair or replace the unit under warranty. Contact the Newton sales office for a returns form which explains the returns procedure. The warranty will be invalidated if the unit is damaged because of improper handling, storage or installation, and in such cases a repair charge may be applicable.

Literature