NBS Source
I'm a manufacturer

Manual Control Point (MCP)

Verified by manufacturer over a year ago

SE Controls

Standard manual control point, designed to allow the Fire & Rescue Service to manually override the smoke control system through a user-friendly interface.

Jump to:
+44 (0)1543 443060 Website

Application

Suitable for smoke ventilation applications.

Description

Standard manual control point, designed to allow the Fire & Rescue Service to manually override the smoke control system through a user-friendly interface.

Compatible with the OSLoop and OS2 control systems (specified separately).


Features and benefits:

  • Design includes an open button and a close/ reset button, which are accessed by lifting the clear front door.
  • Fully complies with pr EN 12101-9; provided in orange (RAL 2011), as required by this standard.
  • System status, operation, fault-finding and cable-monitoring are included within the features of the MCP (OSLoop version only), as required by the standard.
  • Can provide audible signals and faults, in addition to a silence button out-of-view.
  • The MCP (OSLoop version) continuously monitors actuators and connections to smoke detectors (as required by pr EN 12101-9).
  • Event-logging to provide historical user information.
  • Maintenance indication (statutory requirement of the Regulatory Reform Order – Fire Safety).
  • Cover reset push button via access key fob.
  • Reset push button.
  • Activated LED.
  • Power/ healthy LED.
  • Fault LED.
  • Single-action activation cover (replaces glass frangible element).
  • Made in Britain.
  • CE marked.

General information

Shape

Square

Color

Orange

Guidance for specification option:

RAL 2011.

Size

87 x 87 x 22 mm

87 x 87 x 54 mm

Uniclass

Pr_75_50_18_80 Smoke and heat exhaust control panelsPrimary

CAWS

S92/410 Sprinkler alarm panels

S92/410 Control panels

Specification data - Smoke and heat exhaust control panels

Mounting

Flush-mounted.

Surface-mounted.

Accessories

Not required.

Dumb reset key.

Surface mount box.

MCP finger plate.

Sustainability data

Country of product manufacture

United Kingdom

Literature

Understanding Smoke Ventilation Compliance

Understanding Smoke Ventilation Compliance

SE Controls Product Specification Guide

SE Controls Product Specification Guide