In ground unit.
Suitable for trading areas, open air areas with events and exhibitions where temporary power is required. The product is also suitable for traffic light control, CCTV control and telecoms.
It is necessary to ensure a connection to the drainage system. Ensure C35/45 grade concrete all around and underneath.
A paver in ground power unit. This model (Type 3) has a 600 x 600 mm top recessed cover.
It contains an IP 67 electrical panel that holds a combination of three or four sockets either 16A, 32A single phase or three phase plus an additional data panel with 1 to 4 RJ45 sockets.
For added safety the lids are closed during operation. The hinged recessed cover ensures the units are unobtrusive when not in-use. The unit is manufactured in accordance with FACTA and BS EN 124 standards.
The covers are suitable for all types of paving blocks and are manufactured to meet required loadings. They are fabricated in 3, 4, 6 and 8 mm stainless steel as standard. The paving blocks are placed directly adjacent to the frame and bedded using an epoxy or polymer modifier mortar.
Features and benefits:
Applications:
Suitable for trading areas, open air areas with events and exhibitions where temporary power is required. The product is also suitable for traffic light control, CCTV control and telecoms.
It is necessary to ensure a connection to the drainage system. Ensure C35/45 grade concrete all around and underneath.
Material | 1.4301 (304) stainless steel 1.4401 (316) stainless steel Galvanized carbon steel to 140 micron Minimum for Middle East projects. Galvanized carbon steel to BS EN ISO 1461 |
Features | Gas rams, slam lock, four sockets as standard plus RJ45 data point, multiple versions available |
Shape | Square |
Size | 600 x 600 x 450 mm |
Uniclass 2015 | |
CAWS | P31/370 Access covers/ gratings for |
Product Reference | In Ground Power Unit |
Type | KIGU-600/600/450 – Type 3 |
Material | 1.4301 (304) stainless steel1.4401 (316) stainless steelGalvanized carbon steel to 140 micronMinimum for Middle East projects. Galvanized carbon steel to BS EN ISO 1461 |
Loading | BS EN 124 A15Slow moving wheel load: 0.6 tonnes. Kent safety test (unfilled): 1.5 tonnes. BS EN 124 B125Slow moving wheel load: 5 tonnes. Kent safety test (unfilled): 12.5 tonnes. BS EN 124 C250Slow moving wheel load: 6.5 tonnes. Kent safety test (unfilled): 25 tonnes. BS EN 124 D400Slow moving wheel load: 11 tonnes. Kent safety test (unfilled): 40 tonnes. FACTA ASlow moving wheel load: 0.6 tonnes. Kent safety test (unfilled): 0.8 tonnes. FACTA AASlow moving wheel load: 1.5 tonnes. Kent safety test (unfilled): 3.1 tonnes. FACTA AAASlow moving wheel load: 2.5 tonnes. Kent safety test (unfilled): 5.2 tonnes. FACTA BSlow moving wheel load: 5 tonnes. Kent safety test (unfilled): 10.1 tonnes. FACTA CSlow moving wheel load: 6.5 tonnes. Kent safety test (unfilled): 13.2 tonnes. FACTA DSlow moving wheel load: 11 tonnes. Kent safety test (unfilled): 22 tonnes. |
Operation | Closed useOpen use |
Power sockets | EP005Single phase: Two 16 A and One 32 A. EP006Single phase: Two 16 A and Two 32 A. EP008Single phase: Three 16 A and One 32 A. EP009Single phase: Three 16 A. EP010Single phase: Three 32 A. EP011Single phase: Four 16 A. EP012Single phase: One 16 A and Two 32 A. |
Accessories | NoneDP001RJ45 connection. DP002Twin RJ45 connections. DP003Three RJ45 connections. DP004Four RJ45 connections. Dual XLR ConnectionXLR Connection |
Standard product features | Visible frame: 600 x 450 mm. Unit depth: 450 mm Tray depth: 125 mm. Residual current circuit breaker with over current protection (RCBO): The range designed to ensure efficiency and protection. The RCBOs supplied comes standard with every Kent IGU to ensure safety when working with electrical Components and are all IP67 rated. |
Product Options | Power sockets: - Single phase sockets: All single phase Garo sockets are three pin IP67 related which can submerged in water for up to 30 minutes.
- Three phase sockets (available upon request): All three phase Garo sockets are five pin IP67 related which can submerged in water for up to 30 minutes.
Accessories:
|
Platform | Compatible | Version | Certified to |
---|---|---|---|
![]() | Revit 2017 | 1 | 2.0 |
![]() | - | 1 | 2.0 |
Commercial Manhole Cover
In Ground Potable Water Unit – KIGPWU400/450
Kent Hinged Multi Paver KHMP
Kent Hinged Solo Internal Manhole KMHD900/900 HLA
Kent Hinged Vinyl Manhole
Kent Multi Paver KMP
Kent Multi Tray Internal Manhole (KMHD1200/600)
Kent Solo Internal Manhole (KMHD600)
Kent Solo Paver KSP
Kent Triple Seal Odour Tight
© 2020 NBS Enterprises Ltd. All rights reserved.
1 / 2