FR Damper
Compare variants

FR Damper

PRO195 - 5060153111478

Protecta (Polyseam Ltd) Variant:

Protecta FR Damper is used to fire proof ventilation ducts. Consists of steel casing and contains horizontal steel blades, treated with a technically advanced heat expanding graphite.

Jump to:
+44 (0) 1484 421036 www.protecta.co.uk

Application

  • Use to fire proof ventilation ducts which penetrate fire rated constructions such as fire compartments and fire walls, presenting the passage of fire and smoke.
  • The product seals against penetration of fire and smoke, surrounding and inside the ventilation duct.
  • Applicable for drywalls, masonry and concrete walls, timber walls, concrete floors and timber floors.
  • The aperture surrounding the dampers are fire sealed with Protecta fire stopping products.

Description

A fire damper product consist of steel casing and contains horizontal steel blades, treated with a technically advanced heat expanding graphite which closes off the whole damper in a fire. The aperture surrounding the dampers are fire sealed with Protecta fire stopping products.


The damper can be installed in the fire seal and the ventilation ducting attached, or the damper can be connected to the ducting and then fire sealed.


The aperture where the ducts pass through can include one or multiple ventilation ducts. One can also pass through other technical services such as cables, cable trays and pipes within the same aperture.


Features and benefits:

  • Maintenance free and no electrical connection necessary.
  • An aperture can include several dampers and in addition, technical services such as cables, cable trays and pipes.
  • Closes in the area where the fire is located (but not elsewhere), allowing the ventilation system to extract smoke from areas that are not on fire.
  • Keeps the temperature in the duct network lower than 120°C, protecting fans and sensitive units in the system.
  • Insulation of ducts is not necessary.
  • Service life of more than 50 years; the damper will last the same life cycle as the ventilation system.
  • The dampers are designed to fit standard ducting equipment, enabling the ducting system installer to easily fit the dampers.
  • The dampers are attached to the inside of the ducts, giving the benefit of space saving.
  • The damper cab be attached to a vent on one side.
  • Interior climate, installed: Z², Relative air moisture up to 85% and temperatures between five and 40 °C.
  • Trigger-temperature in fire: 100°C.
  • Full closure temperature: 160°C.
  • Time to full closure: From 50 seconds to two minutes.
  • Expansion rate graphite: 15.5 to 17.
  • Density graphite: 2.6 kg/L.


The 'close in and pull out' principle:

A combined ‘close in and pull out’ solution is one that prevents the spread of fire by closing off the fire inside the fire compartment, using the ventilation system outside the area of the fire to pull out any smoke that filters out through the fire compartments constructions.


Dust formation and general maintenance:

Tests conducted on Protecta® FR Damper to determine dust formation inside the damper, has shown that dust does not collect inside the damper, and no more than in any other components in the ventilation system. The dust tends to be blown through the dampers as long as the ventilation system is in constant operation and installed in normal indoor environments (Z2).

General information

Shape

Other

Color

Red

White

Finish

Galvanized

Material

Steel

Graphite

Uniclass

Pr_65_65_24_29 Fire and smoke dampersPrimary

CAWS

U90/443 Dampers, fire and smoke

U90/443 Dampers, fire and smoke

Specification data - Fire and smoke dampers Enhanced data

Standard

-

Test

To BS EN 1366-12:2014 and BS EN 1363-1:2012.

Aerodynamic performance

To BS EN 1751:2014, Class C and BS EN ISO 5135:1998.

Arrangement

Multi-blade.

Material

Galvanized steel and graphite.

Diameter

63 mm.

Weight

0.51 kg.

Length

150 mm.

Bespoke.

Longer and shorter dampers can be manufactured

on request. Consult manufacturer for details.

Colour

Steel with section of red.

To identify placement of the fire seal.

Pressure

Pressure in fire.

300 Pa.

Minimum.

Installation temperature

+5 °C to +50 °C.

Third-party certification

BREEAM EC1PLUS or M1, approved and Warringtonfire Testing and Certification Ltd (UKAS accredited).

Environmental information

Country of product manufacture

United Kingdom

Literature

FR Damper - Intumescent Fire Damper For Fireproofing Ventilation Ducts

FR Damper - Intumescent Fire Damper For Fireproofing Ventilation Ducts

Protecta FR Damper - UL-EU Certificate

Protecta FR Damper - UL-EU Certificate