NBS Source
I'm a manufacturer

FireMaster® NVS™ Simplex Horizontal - Horizontal Active Fire Curtain

Verified by manufacturer 6 months ago

Coopers Fire Ltd

Developed by the manufacturer to protect all building types from airports to domestic houses.

Jump to:
BIM object icon
+44 (0)23 9245 4405 Website

Application

  • Suitable to be used to form a virtually continuous barrier as a fire separating element.
  • Suitable for use from airports to domestic houses and developed by the manufacturer to protect all building types.

Description

An electrically operated active fire curtain barrier assembly. The barrier assemblies comprises a fire-resistant fabric wound on to a steel roller, powered by an internal 24 V d.c. electric motor, enclosed within a 1.2 mm-thick mild steel box. The edges of the curtain are retained inside side guides, providing pressure resistance of at least 20 Pa. The 24 V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position.


The barrier assemblies have been tested to the requirements of BS EN 14600:2005 for ‘Durability of Self-Closing’ (500 cycles on primary power and an additional ten cycles using back-up power; closing speed of 0.06 m/s). The barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 + A1:2018 for ‘Fire Resistance’ (120 minutes integrity). The barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 + A1:2018 for ‘Radiant Heat Flux’ (20 minutes).


Operation:

Barrier assemblies commence movement upon initiation of BMS alarm or power or system failure, and fully deploys to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function. Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit. In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. At the end of the period, the barrier assembly will deploy.


Fire resistance:

120 minutes (2 hours) integrity.


Radiation resistance:

20 minutes.


Product certification, performance and/ or testing:

  • Complete active fire curtain barrier assemblies are certified by an independent accredited certification body operating to ISO/ IEC 17065:2012.
  • Complete active fire curtain barrier assemblies have been tested for fire resistance to BS EN 1634-1. The barrier assembly achieved 90 minutes integrity and 20 minutes radiation.
  • Complete active fire curtain barrier assemblies have passed tests for durability to BS EN 14600:2005 (500 cycles).
  • Motor(s) used within active fire curtain barrier assemblies have passed elevated temperature operational tests to BS 8524-1:2013, Annex G.


Approving standards:

The following standards apply to this product:

  • BS EN 1634-1:2018, Fire resistance and smoke control tests for door, shutter and, openable window assemblies and elements of building hardware. Fire resistance tests for doors, shutters and openable windows.
  • BS EN 1363-1:1999, Fire resistance tests – Part 1: General requirements.
  • BS EN 14600, Doorsets and openable windows with fire resisting and/ or smoke control characteristics – Requirements and classification.
  • BS 8524-1:2013, Annex G, “Test method for reliability of motor operation at elevated temperatures”.
  • BS EN ISO 1716:2010, Reaction to fire tests for products. Determination of the gross heat of combustion (Calorific value).
  • BS 476 Pt 6, Fire tests on building materials and structures. Method of test for fire propagation for products.
  • BS 476 Pt 7, Fire tests on building materials and structures. Method of test to determine the classification of the surface spread of flame of products.
  • BS EN 13823, Reaction to Fire Tests – Single Burning Item.
  • BS EN 13501-1:2007+A1:2009, Fire classification of construction products and building elements. Classification using test data from reaction to fire tests.
  • BS EN ISO 14184-1:2011. Textiles. Determination of formaldehyde. Free and hydrolysed formaldehyde (water extraction method).
  • BS EN ISO 9001:2015 Quality management system.
  • BS EN ISO 14001:2015, Environmental management system.

General information

Color

Other

Finish

Galvanized

Powder-coated

Material

Fabric

Shape

Rectangle

Width

Bespoke

Height

Bespoke

Warranty description

One year

Guidance for specification option:

From date of commissioning.

Uniclass

Pr_25_80_79_38 Horizontal active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Horizontal active fire curtain barriers

Standards

-

Test standards

Compliant to BS EN 1634-1:2018.

Size

Guidance for specification option:

Insert requirement.

Performance

-

Fire resistance

120 minutes (2 hours) integrity.

Barrier units

Flexible metallic fabric.

Guidance for specification option:

  • The main curtain fabric type is EFP™ A1, which is a stainless steel wire reinforced glass fabric fire barrier. It has an area weight of 665 g/m²-5%, +10%.
  • The curtain fabric offers dimensional stability and is non-combustible to BS EN 13501-1 + A1– Reaction to Fire.
  • The fabric has passed testing to BS 476-6 (Method of test for fire propagation for products).
  • The fabric has passed testing to BS 476-7 (Method of test to determine the classification of the surface spread of flame for products).
  • The fabric has passed testing to BS EN 1634-1, BS EN 1363-1, BS EN 1362-2 and BS EN 1634-3 (Fire/Smoke Resistance).
  • The fabric has passed testing to BS EN ISO 1716 (Determination of the Heat of Combustion for Building Products).
  • The fabric has passed testing to BS EN 13823 (Reaction to Fire Tests – Single Burning Item).
  • The fabric has passed testing to HSG 248 (Analysis of Material for the presence of Asbestos).
  • The fabric has passed testing to BS EN 14184-1 (Textiles – Determination of Formaldehyde – Part 1: Free and hydrolysed formaldehyde (water extraction method).
  • The fabric has a Classification of Reaction to Fire Performance in accordance with EN 13501-1:2007 +A1:2009 of ‘A1’.

Deployment

Full.

Activation

Commences movement upon initiation of alarm or power or system failure.

Accessories

None.

Visual alert system.

Guidance for specification option:

Light warning system when mains or emergency power is available.

Voice warning.

Guidance for specification option:

Audio or spoken multi message facility when mains or emergency power is available.

Frame colour/ finish

Guidance for specification option:

Insert requirement.

Type

Face fixed.

Reveal fixed.

Finish

Not applicable.

Galvanized steel.

Powder coated.

Guidance for specification option:

Available upon request, insert colour requirements.

Zintec

Painted

Fixing

Face fixed.

Top fixed.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Recyclability

Coopers Fire offer a take back service where product is broken down into component parts.
Metal = recycled
Fabric = recycled
WEEE = disposed through correct channels

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

0 %

BIM objects

BIM object icon

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit

Revit 2017

1

IFC
-

1

Literature

FireMaster® Concertina™  Active Fire Curtain Barrier

FireMaster® Concertina™ Active Fire Curtain Barrier

Similar products from Coopers Fire Ltd

FireMaster® NVS™ Horizontal Duplex™ - Horizontal Active Fire Curtain

FireMaster® NVS™ Horizontal Duplex™ - Horizontal Active Fire Curtain

SmokeStop DH120 Smoke Curtain

SmokeStop DH120 Smoke Curtain