FireMaster® A1

Application

Designed to form a virtually continuous barrier as a fire separating element.

Description

An electrically operated FireMaster® A1 active fire curtain barrier assembly used to form a virtually continuous barrier as a fire separating element.

FireMaster® A1 active fire curtain barrier assemblies comprise a woven steel and glass fabric wound on to a steel roller, powered by an internal 24V dc electric motor, enclosed within a 1.2 mm steel box. A bottom bar is fitted to the bottom edge of the curtain providing tension to the curtain with sufficient weight for the curtain to ‘fail-safe by gravity’.

The 24V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position.

FireMaster® A1 active fire curtain barrier assemblies have been tested to the requirements of BS EN 14600:2005 for ‘Durability of Self-Closing’ (500 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.08m/s).

FireMaster® A1 active fire curtain barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 for ‘Fire Resistance’ (120 minutes integrity).

FireMaster® A1 active fire curtain barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 for ‘Radiant Heat Flux’ (30 minutes).

Operation:

FireMaster® A1 active fire curtain barrier assemblies commence movement upon initiation of alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function.

Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.

In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. At the end of the period, the Barrier assembly will deploy.

Period of fire resistance:

  • 180 minutes integrity (single).
  • 120 minutes integrity (overlapped).

Period of radiation:

  • 37 minutes <15 kW/m² (single).
  • 51 minutes <15 kW/m² (overlapped).

Classification:

  • Single: E180 EW30 C0 Grade 1.
  • Overlapped: E120 EW30 C0 Grade 1.

Product certification, performance and/ or testing:

  • Complete barrier assemblies are certified by an independent accredited certification body operating to ISO/IEC 17065:2012.
  • Complete barrier assemblies have been tested for fire resistance to BS EN 1634-1, as required by BS 8524-1. The Barrier assembly achieved 120 minutes Integrity and 30 minutes Radiation.
  • Complete barrier assemblies have been tested for impact to BS 5234-2 as required by BS 8524-1
  • Complete barrier assemblies have been tested for reliability, durability and self-closing to BS EN 14600 as required by BS 8524-1
  • Complete barrier assemblies have been tested for gravity fail-safe as required by BS 8524-1
  • Motor(s) used within barrier assemblies the above tests have been tested for operation at temperatures of 400 °C as required by BS 8524-1
  • The fabric used in FireMaster® A1 active fire curtain barrier assemblies have been tested to BS EN 1634-3
  • The fabric used in FireMaster® A1 active fire curtain barrier assemblies have been tested to BS EN ISO 1716
  • The fabric used in FireMaster® A1 active fire curtain barrier assemblies have been tested to BS 476 pt6 & pt7
  • The fabric used in FireMaster® A1 active fire curtain barrier assemblies have been tested to BS EN 13823
  • The fabric used in FireMaster® A1 active fire curtain barrier assemblies have been tested to BS 6853
  • The fabric used in FireMaster® A1 active fire curtain barrier assemblies have been classified as ‘A1 to EN 13501-1

The following standards apply to this product:

  • BS 8524-1, Specification for active fire curtain barrier assemblies
  • BS EN 1634-1:2008, Fire resistance and smoke control tests for door, shutter and, openable window assemblies and elements of building hardware. Fire resistance tests for doors, shutters and openable windows
  • BS EN 1634-3:2004, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware. Smoke control test for door and shutter assemblies
  • BS EN 1363-1:2012, Fire resistance tests – Part 1: General requirements
  • BS EN 1363-2:1999, Fire resistance tests – Part 2: Alternative and additional procedures
  • BS EN 13501-2:2007+A1, Fire classification of construction products and building elements. Classification using data from fire resistance tests, excluding ventilation services rating
  • BS EN 14600:2005, Doorsets and openable windows with fire resisting and/ or smoke control characteristics. Requirements and classification
  • BS EN ISO 1716:2010, Reaction to fire tests for products. Determination of the gross heat of combustion. (Calorific value)
  • BS 476-6, Method of test for fire propoagation for products
  • BS 476-7, Method of test to determine the classification of the surface spread of flame for products
  • BS 6853: 1999 – Annex D.8.4, Methods for measuring smoke density
  • BS EN 13501-1:2007+A1:2009, Fire classification of construction products and building elements. Classification using test data from reaction to fire tests
  • BS EN ISO 14184-1:2011. Textiles. Determination of formaldehyde. Free and hydrolised formaldehyde (water extraction method)
  • BS EN ISO 9001:2015, Quality management system
  • BS EN ISO 14001:2015, Environmental management system

Application:

Designed to form a virtually continuous barrier as a fire separating element.

General information

Finish

Galvanised

WarrantyDescription

One year warranty from date of commissioning

Uniclass 2015

Pr_30_59_84_73 Roller shuttersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Roller shutters

Product Reference

FireMaster® A1

FireMaster® A1 (S)

With smoke seals. BS EN 1634-1

Standard

BS 8524-1, BS EN 1634-1 (type dependant), BS EN 1363-1, BS EN 1363-2, BS EN 1634-3, BS EN 13501-4 +A1, BS EN 14600, BS EN ISO 1716, BS EN 13501-1 +A1, BS EN ISO 14184-1, BS 6323-5, FireMaster® A1 only: BS EN 13823

Opening sizes

Insert requirements.

Performance

-

Air permeability:

<3 m³/h/m at ambient temperature at 25 Pa (0.1 in water) in accordance with BS 8524-1 Annex F

Extras

None

Beam protection and obstruction warning

Emergency retract

Split drop delay

Visual alert system

Voice warning

Uniclass 2015 Title

Roller shutters

Standard product features

Material:

The main curtain fabric type is EFP™ A1, which is a stainless steel wire reinforced glass fabric fire barrier. It has an area weight of 665g/m2 -5% +10%.

The curtain fabric offers dimensional stability and is non-combustible to BS EN 13501-1 + A1– Reaction to Fire.

The fabric has passed testing to BS EN 1634-1, BS EN 1363-1, BS EN 1362-2 and BS EN 1634-3 (Fire/Smoke Resistance)

The fabric has passed testing to BS EN ISO 1716 (Determination of the Heat of Combustion for Building Products)

The fabric has passed testing to BS EN 13823 (Reaction to Fire Tests – Single Burning Item)

The fabric has passed testing to BS 6853 (Methods for measuring smoke density)

The fabric has passed testing to HSG 248 (Analysis of Material for the presence of Asbestos)

The fabric has passed testing to BS EN 14184-1 (Textiles – Determination of Formaldehyde – Part 1: Free and hydrolysed formaldehyde (water extraction method)

The fabric has a Classification of Reaction to Fire Perfromance in accordance with EN 13501-1:2007 +A1:2009 of ‘A1’.

Warranty description:

One year.

Country of manufacture:

United Kingdom.

Digital objects

Platform Compatible Version Certified to
Revit

Revit 2017

2

2.0
IFC
-

2

2.0
Download now from NBS National BIM Library