Fire rated cables, light duty (500 V).
A fire survival MI wiring cable system designed for versatility and ultimate fire survival performance. Provides a solution to many difficult and demanding wiring installations making a permanent and dependable wiring cable system for all low and medium voltage applications. Safe in hazardous installations and radioactive environments. Exceeds all worldwide fire performance standards. The Pyro MI Cable System is suitable for domestic, commercial and industrial applications. The cables are manufactured, tested in accordance with LPCB and BS EN 60702-1, BS 8434-2, BS 5839-1 Clause 26.2 (Enhanced), BS EN 50267-1, and BS EN 50200 Class PH 120.
Pyrotenax Terminations are tested in accordance with BS EN 60702-2. Pyrotenax Terminations are certified for use in potentially explosive atmospheres. Glands - Baseefa08ATEX0327X and IECEx BAS 08.0107X Increased Safety Seals - Baseefa02ATEX0194U.
Features and benefits:
With a basic inorganic construction of a copper sheath and conductors, together with a mineral insulant, the cable provides dependability, versatility and permanence. This construction, with the melting points of 1083°C and 2800°C for the copper and the insulant respectively, provides the unsurpassed fire survival properties which enable the cable to continue to carry current at temperatures in excess of 1000°C.
Pyro Twist Cables:
Pyro Twist is a range of communication and signal cables for life preservation and integrated building management systems. They have been developed from the proven characteristics of Pyro MI to maintain the security of vital signals in communication and data networks, particularly in hostile conditions.
Seals and Insulators:
A seal is normally required at each end of a Pyrotenax MI Cable to provide a means of electrical connection. The Standard Brass 105°C Seal is suitable for the majority of general wiring applications. However since Pyrotenax Cables are used in a wide variety of environments, a comprehensive range of seals and insulators are available to suit every need. A complete termination comprises a seal to provide a means of electrical connection and a gland to secure the cable into the appropriate apparatus.
Externally threaded brass compression glands are available with ISO metric threads as standard. Other thread forms are available on request. Internally threaded 20 mm ISO metric brass compression glands are available for the full range of two, three and four conductor, 500 volt light duty cables.
Uniclass 2015 |
Product Reference | Fire Rated Cables, Light Duty (500 V) |
Type | Extensive range available, consult literature and insert requirements. |
Seal | Fire resistant sealHigh temperature glazed insulatorIncreased safety sealStandard seal |
Product Options | Seal: - Fire resistant seal: When fire resistance is required, standard Pyrotenax 105°C seal Ref. RPS can be used provided that the standard PVC sleeving is replaced by silicon elastomer coated glass braided sleeving Ref. RZPS. Such seals will pass a circuit integrity test, essentially as given in BS 6387 for category C, with seals in a 950°C flame for three hours. - High temperature glazed insulator: For environments up to 250°C, a glazed insulator can be constructed as follows:
- Increased safety seal: Continuous operating temperature range -20°C to +85°C. Intended for use with type of protection 'e' in potentially explosive atmospheres. Available in plain and earth tail. Typical seal references: Plain-RPA2H6 20. Earth Tail-RPAL2H6 25. - Standard seal: Continuous operating temperature range - 80–105°C. These standard seals are suitable for all general wiring applications. Available in plain or earth tail. Typical seal references: e.g. Plain-RPS 2L2.5 20. Earth Tail-RPSL2L2.5 20. e.g. Plain-RPS 2H6 20. Earth Tail-RPSL2H6 20. |