Verified by manufacturer 1 month ago
Alcumus SafeContractor
Certificate type
Constructionline
Certificate type
ISO 9001 Quality Management
Certificate type
dhf certificate
Certificate type
Two Hour Fire and Radiant Heat Resisting Curtain.
Any internal application where fire compartmentation is required but is particularly suited for retail malls, offices, receptions, foyers, lift lobbies, lift Doors, open-plan private residencies.
These fire curtains are specifically designed to provide fire compartmentation and a protected means of escape all within a compact, aesthetically pleasing yet robust and reliable system.
Utilising a fully tested woven glass fabric with stainless steel wire reinforcement, the Fibreroll E120 Rolling Fire Curtain provides not only up to two-hour fire integrity between fire compartments but also a reduction in radiated heat to such a large extent that it meets the requirements for a rating of EW30, including Rigid Structures
and Flexible Structures
Features and benefits:
Color | Grey |
Finish | Galvanized Powder-coated Textured Manufacturer guidanceSide guides, bottom rail and coil casing supplied with polyester powder coated finish to alternative RAL colour from standard range. |
Material | Steel |
Shape | Square Rectangle |
Length | Bespoke |
Width | Bespoke Guidance for specification option: Bespoke sizes. Single roller - maximum 5000mm wide Multiple rollers - maximum width is unlimited |
Height | Bespoke Guidance for specification option: Bespoke sizes. Single roller - maximum 8000mm high Multiple rollers - maximum 6000mm high |
Warranty description | One year |
Uniclass | |
CAWS | L20/809 Fire-resisting and smoke control doors/ door assemblies/ doorsets/ roller shutters and curtains – accredited installer L20/810 Fire-resisting and smoke control doors/ door assemblies/ doorsets/ roller shutters and curtains – contractor installed |
Product range |
System performance | E120 & EW30 |
Fire barriers | Vertical active fire curtain barriers. |
Execution | Installing active fire curtain barrier assemblies. |
System completion | Verification of performance. |
Test Standard | To BS EN 1634-1. Guidance for specification option: all in accordance with EN 13501-2 and EN15269-11. |
Opening size | 5000 x 8000 mm. Manufacturer guidanceInsert requirement. |
Fire resistance | E30. E60. E120. Guidance for specification option: Available up to 16254 x 6740 mm (clear width x clear height). EW30. |
Activation | In a fire condition, activation is initiated by a normally closed volt free contact from the fire alarm system or, where on a fire exit route, local heat detector. Closure is by gravity with a controlled descent. |
Accessories | None. Emergency retract. Local heat detector. Obstruction warning (via light curtain). Sounder beacon. |
Colour | Galvanised Steelwork PPC Option Available |
Fixing | Face-fixed. Soffit-fixed. Suspended (to a maximum of 500 mm). |
Weight | Curtain: 0.78 kg/m², Barrel/casing: 30 kg/m² (approx). Guidance for specification option: Approximately. |
Standards | To BS EN 1634-1. Manufacturer guidanceBS EN 8524 approval option available. |
Radiation | Reduction of 15kW/m² to EW30 classification. |
Contains Red List materials | No |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Recyclability | 50% |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 0 % |