Durasteel Fire Barrier
Compare variants

Durasteel Fire Barrier

Promat UK Variant:

Fire barrier for use in partitioning, ducting, door and ceiling applications.

Jump to:
+44 (0)800 145 6033 www.promat.com

Application

DURASTEEL® systems have been used successfully for many years, including rail and metro projects, military developments and in commercial, pharmaceutical and petrochemical facilities.

Description

DURASTEEL® has been developed and supported through rigorous testing for use in partitioning, ducting, door and ceiling applications, with a wide range of specifications available.


Features and benefits:

  • DURASTEEL® systems combine lightness, strength, impact resistance and durability with exceptional fire resistance.
  • These systems remain resistant to firefighters’ hoses, leaving them capable of performing their original function even in the aftermath of a fire.
  • DURASTEEL® systems have been used successfully for many years, including rail and metro projects, military developments and in commercial, pharmaceutical and petrochemical facilities.
  • The gap in the Durasteel and Promatect 250 board facing is covered with a Durasteel and Promatext 250 board cover panel.


Construction:

  • Perimeter channels fastened to surrounding construction with M10 or M12 all-steel expanding anchors (or equivalent) at 500 mm maximum centres.
  • Vertical channels at maximum 1200 mm centres. Horizontal and vertical channel members either welded together or joined with steel angle cleats, minimum 60 x 60 x 3 mm thick x 60 mm long, fastened to each channel member with two M10 steel bolts and nuts.
  • For barriers with insulation only: 9.5 mm DURASTEEL® fillet fixed on both sides of channel. Fillet strips to overlap channel by minimum of 20 mm on both sides.
  • Single layer of 9.5 mm DURASTEEL® fixed on one side of channel with M5.5 steel self-drill and tap Tek screws at 250 mm nominal centres. Fixings a minimum of 12 mm from edge of sheet and a maximum of 50 mm from corners. Length of fixing to be sufficient to ensure appropriate penetration of screw thread in accordance with screw manufacturer’s recommendations.
  • Vertical board joints coincide with studs, horizontal board joints are backed by steel channel the same size as the vertical studs.

General information

Finish

Studded

Material

Steel

(Anchors).

Shape

Rectangular

Uniclass 2015

Ss_25_10_30_70 Rigid sheet partition systemsPrimary

CAWS

K10/125 Metal stud partition system

K10/30 Metal stud

Specification data - Rigid sheet partition systems Enhanced data

Framing

Perimeter channels fastened to surrounding construction with M10 or M12 all-steel expanding anchors, vertical channels at maximum 1200 mm centres.

Horizontal and vertical channel members either welded together or joined with steel angle cleats.

Insulation

No insulation.

Integrity only.

Cavity fire barriers

Dependent on insulation specified. Fire barriers have 240 minutes' integrity. All fire barriers are resistant to fire attack from either face.

Fasteners

Manufacturer's standard.

Product Reference

Durasteel Fire Barrier

OverallWidth

Dependent on insulation specified.

89.5 mm.

Size:

Channels up to 6 m are 80 x 60 x 3 mm.

Vertical and horizontal channels.

Sound reduction

33 dB.

(Estimated).