NBS Source
I'm a manufacturer

CFS-CT Firestop Coating

Verified by manufacturer 1 month ago

Hilti (Gt Britain) Ltd Third party certifications:
  • UK Technical Assessment (UKTA)

    UK Technical Assessment (UKTA)

    Certificate type

  • European Technical Approval (ETA)

    European Technical Approval (ETA)

    Certificate type

Firestop Coating

Jump to:
+44 (0)800 886100 Website

Application

  • Mixed penetrations in flexible and rigid walls from 100 mm and rigid floors from 150 mm
  • Cables, cable bundles, cable trays and cable conduits
  • Non-combustible (metal) pipes with non-combustible insulation
  • Non-combustible (metal) and composite pipes with combustible insulation in combination with CFS-B firestop bandage or CFS-C P firestop collar
  • Combustible pipes in combination with CFC-C P or CFS-C firestop collars or CFS-W firestop wrap


Description

Firestop coating for firestop boards.


Features and benefits:

  • EN testing for wide range of applications
  • Single-layer coating – provides labour savings over multilayer coatings
  • Dry film thickness 0.7 mm – up to 30% material savings compared to multilayer coatings
  • Paintable, even on rough surfaces
  • Flexible coating dries quickly to form an elastic protective layer

General information

Color

White

Shape

Formless

Uniclass

Pr_35_31_68_43 Intumescent protective coatingsPrimary

CAWS

P12/340 Intumescent mortar

P12/37 Intumescent mortar

Specification data - Intumescent protective coatings

Colour

White.

Application temperature

5–40°C.

Temperature resistance

-40 to +100°C.

Bacteria resistance (to EN846)

4 mm/ day.

Curing time

1 mm/ day.

Third party certifications

UK Technical Assessment (UKTA)

UKTA22 0052 CFS-CT B Board

European Technical Approval (ETA)

ETA-11/0429 for CFS-CT Firestop Coating Double Board for Penetrations