Type A unit (with booster pump)
Hybrid spray and evaporative, close control adiabatic humidifier.
Suitable for close control adiabatic humidification with hygienic performance requirements.
Hybrid spray and evaporative, close control adiabatic humidifier which combines spray and evaporative technologies.
Features and benefits:
System components:
Shape | Rectangle |
Color | Silver |
Size
| 800 x 500 x 250 mm Central unit, H x W x D. |
Uniclass |
Accessories | Not required.Water supply flushing valve.Allows water to be drained from the pipework, between the RO filter and the central pump station. In-duct humidistat.Water softener.RO water treatment system.Leak monitoring.External pipe flushing set.BMS gateway board.LonWorks or BACnet IP/ BACnet MSTP. Mounting frame for pump station and control unit.Silicon-free.Droplet eliminator.For air velocities 3–4 m/s. |
Dimensions
| Central unit: 800 x 500 x 250 mm, Control unit: 450 x 315 x 190 mm. |
Weight | Central unit: 54 kg, Control unit: 14 kg. Approximate. |
Performance | 0–1000 kg/h.
|
Pressure | 3–7 bar. Nozzle pressure. |
CapacityNozzle capacity sizes at 4 bar. | 1.5 kg/h. 2.5 kg/h. 3.0 kg/h. 4.0 kg/h. 5.0 kg/h. |
Quality | Reverse osmosis water: 0.5–15.0 μS/cm. Water quality requirement. |
NominalSupplyVoltage | 200–240 V a.c., 50–60 Hz (maximum 6 A). Supply voltage and current control unit. |
Pump control | Continuous with frequency converter. Control booster pump motor, Type A unit only. |
Power consumption | 55–65 VA. Control unit. |
Motor | Booster pump motor rating: 10 VA per 10 kg/h spray capacity (approximate), with frequency converter. Type A unit only. |
RelativeHumidityControl accuracy. | 7 steps: ±3% RH, 15 steps: ±2% RH, 31 steps: ±2% RH. |
Communication hub | Remote operating and fault indication board, Modbus RTU, BACnet IP and BACnet MSTP slave mode. |
PressureDrop | 40 Pa (approximate). At 2 m/s. |
MaximumVelocityMaximum air velocity. | 3 m/s. Without droplet eliminator. 4 m/s. With droplet eliminator. |
Filter | F7 (EU7) or better air filter quality before humidifier. |
Maximum temperature | 60°C. Recommended air temperature before humidifier. |