CFS-CU
Application

  • Cable penetrations in flexible walls from 100 mm and rigid walls and floors from 150 mm.
  • Cables, cable bundles and 50 mm PVC pipes.
  • Temporary sealing of openings in floors and walls through the construction phase.

Description

Intumescent cushion for firestop applications in temporary installations.

Features/ Benefits:

  • Quick and easy installation.
  • No special tools required.
  • Fully functional immediately after installation.
  • Re-usable and thus economical.
  • Very economical in use thanks to optimized cushion dimensions.
  • Fire resistance rating of up to four hours.
  • ETA-08/0213.

Applications:

  • Cable penetrations in flexible walls from 100 mm and rigid walls and floors from 150 mm.
  • Cables, cable bundles and 50 mm PVC pipes.
  • Temporary sealing of openings in floors and walls through the construction phase.

Suitable substrates:

Drywall, concrete and masonry.

General information

Uniclass 2015

Pr_25_80_81_43 Intumescent pillowsPrimary

CAWS

P12/345 Intumescent pillows

Specification data - Intumescent pillows

Product Reference

CFS-CU L

300 x 170 x 30 mm (l x w x h).

CFS-CU M

300 x 80 x 30 mm (l x w x h).

CFS-CU S

300 x 40 x 30 mm (l x w x h).

Standard product features

Colour:

White.

Fire resistance:

Up to four hours, dependent on substrate and application.

Technical properties:

  • Application temperature: -20 to +40°C.
  • Temperature resistance: -40 to +50°C.
  • Reaction to fire (to BS EN 13501-1): B-s1, d0.
  • Mould and mildew resistance (to BS EN ISO 846): Class 0.

Third party certifications
  • ETA: 08/0213
Similar products from Hilti (Gt Britain) Ltd