Verifisert av produsent for 14 døgn siden
Single No Smoke Seals
IFCC
Sertifikattype
smas WORKSAFE
Sertifikattype
Vertical active fire and smoke curtain barrier providing up to 120 minutes integrity and EW120 radiation control, achieving 10.7 kW/m² at 120 minutes, tested to BS 8524-1 and installed to BS 8524-2.
Vertical active fire and smoke curtain barrier suitable for a wide range of internal fire compartmentation and smoke control applications, including protected means of escape, atria, lobbies, reception areas, corridor separation, openings in fire-resisting walls, boundary protection, escalators, stairwells, lift shafts and lift lobbies.
Regularly specified within hospitals and healthcare facilities, schools and universities, hotels, high-rise and mixed-use developments, commercial offices, retail environments, stadia, museums and galleries, as well as transport infrastructure, industrial and utility installations. Also suitable for defence, custodial, policing and secure environments where reliable fire and smoke containment is required.
The Flameshield EW120 Vertical Active Fire and Smoke Curtain Barrier is an electrically operated, gravity fail-safe fire and smoke control system designed to form a virtually continuous fire-resisting barrier within a building. The system delivers 120 minutes fire integrity and EW120 radiation performance, maintaining radiation levels below 15 kW/m² and achieving 10.7 kW/m² at 120 minutes, supporting occupant tenability and protected means of escape strategies.
The barrier assembly comprises a carbon steel barrel and integrated 24 V d.c. electric motor, incorporating a high-performance flexible fire curtain fabric capable of withstanding temperatures in excess of 1000°C. Barrel deflection is compliant with BS 6323-5, ensuring stability and reliability across a wide range of opening sizes. A two-section bottom rail provides controlled descent, consistent tension and dependable gravity fail-safe deployment in the event of power or system failure.
The Flameshield EW120 system is designed for discreet architectural integration and can be concealed above ceiling lines. End plates, guides and hoods are available in a range of finishes, allowing the system to blend seamlessly with interior design requirements without compromising fire or smoke performance.
A two-stage closing operation, timed delay options and a comprehensive range of ancillary safety devices are available, including egress switches, access switches, obstruction detection and heat and smoke activation. All ancillary equipment is fully tested in accordance with Annex H of BS 8524-1. Optional audible and visual warning systems, including voice warning devices, enhance safety during deployment.
The system is fully compliance-tested, incorporates low-maintenance components, and is capable of full reset following fire testing without the need for specialist engineer attendance. Manufacture and construction align with tested assemblies and relevant sections of BS EN 16034, ensuring consistent performance and regulatory confidence.
Independent fire, radiation and smoke containment testing has been undertaken and approved by Warrington Fire Research Centre and Exova, in accordance with BS 8524-1, BS EN 1634-1 (fire resistance and radiation performance) and BS EN 1634-3 (smoke containment).
Features and benefits:
Radiation:
Farge | Other ProdusentveiledningFull selection of RAL colours available. |
Overflatebehandling | Powder-coated Mill ProdusentveiledningC3 corrosion class available as standard. Advanced durability to corrosion class C3h on application. |
Materiale | Carbon steel Stainless steel |
Form | Rectangle |
Lengde | Bespoke |
Bredde | Bespoke |
Høyde | Bespoke |
Garantibeskrivelse | One year Veiledning for spesifikasjonsvalg: Extended warranty available on application. |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
SKU Code | FS EW120 |
Klassifiseringsdata | |
Standards | |
Barrier assemblies | To BS 8524-1. |
Test standards | Vertical, horizontal and angled to BS EN 1634-1. BS EN 1634-3. |
Third-party certification | Warrington Fire Report 406515. |
Size | Veiledning fra produsentMaximum size (width x height): 8000 x 8000 mm. (32 m²). Insert requirements. |
Performance | |
Smoke containment | No smoke seals. |
Fire resistance | 60 minutes. 120 minutes. |
Accessories | Partial Drop. Veiledning for spesifikasjonsvalg: The barrier shall have the facility to deploy to a pre-determined position to allow escape and initial smoke containment. The partial close position shall be site adjustable with an adjustable wait time in the partial close position of up to 10 minutes Emergency Retract. Veiledning for spesifikasjonsvalg: The barrier can have an emergency retract interface for escape and emergency access. The interface shall be volt free, normally open (close on operation). The signal required shall be momentary with a site adjustable retract time. The emergency retract facility shall be operational as long as there is primary / secondary power available. BMS Interface. Veiledning for spesifikasjonsvalg: The barrier has volt free c/o contacts to indicate whether the barrier is fully open or fully closed. Single Photo Cell. Veiledning for spesifikasjonsvalg: Tested and Passed by Exova to BS 8524-1 Annex H Audio / Visual / Spoken Warning Unit. Veiledning for spesifikasjonsvalg: The barrier has a volt free contact which indicates an active c/o (change over) contact which indicates an active alarm signal. An Audio / Visual / Spoken warning unit can be interfaced with this using power supplied by the primary / secondary source or via an external source. Multi-beam Detection. Veiledning for spesifikasjonsvalg: A multi-beam detection system is required when the barrier assembly is intended to protect a means of escape route. For more information, see BS 8524 - 2.5.8.5.2. |
Fabric | 4415-2-B1 fabric. Veiledning for spesifikasjonsvalg:
|
Barrel | Carbon steel tube. Veiledning for spesifikasjonsvalg: Fire curtain barrels are manufactured from carbon steel tube, tube size dependent on the overall size of the unit and deflection calculated to conform to British Standards. |
Finishes | Powder-coated. Mill. Veiledning fra produsentC3 corrosion class available as standard. Advanced durability to corrosion class C3h on application. |
Farge | Veiledning fra produsentConsult manufacturer and insert requirements. Full selection of RAL colours available. |
Inneholder Red List-materialer | No |
Opprinnelsesland for materiale | United Kingdom |
Produksjonsland for produktet | United Kingdom |
Plassering av produksjonsanlegg | |
Materiale | Carbon steel Stainless steel |
Forventet liv | Ten year Veiledning for spesifikasjonsvalg: Lifetime under BS 8524-2. Veiledning fra produsentLifetime under BS 8524-2. |
Dette BIM-objektet er forfattet for å oppfylle kravene i
Finn ut mer om
| Plattform | Kompatibel | Versjon |
|---|---|---|
| - | 1 | |
| - | 1 |
Fire Curtain Flameshield 8524 (S) Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain
Fire Curtain Flameshield 8524 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain
Fire Curtain Flameshield 8524 Overlapping Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire Curtain
Fire Curtain Flameshield 8524 Vertical Active Fire Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire Curtain
Fire Curtain Flameshield EVO Vertical Active Fire and Smoke Curtain Barrier – BS EN 1634-1 Tested - Vertical Active Fire and Smoke Curtain
Fire Curtain Flameshield EW120 Max/S Vertical Active Fire and Smoke Curtain Barrier – BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain
Fire Curtain Flameshield EW120 S Vertical Active Fire and Smoke Curtain Barrier - BS 8524-1 & BS 8524-2 Tested - Vertical Active Fire and Smoke Curtain